Transformer · Autotransformer · Boost and buck

Buck-Boost Transformer Calculator

Enter the voltage you have, the voltage your load needs and its amps. See the output voltage, the unit size in kVA, the max load current and the fuse or breaker limit.

By · Updated · How results are sourced

1Supply and load

Phase

Line and load must have the same number of phases. A buck-boost transformer cannot change single phase to three phase.

V

Voltage on the line side. Nominal or measured. A winding is not run above its rated 120 or 240 V, so a supply above 240 V leaves fewer options.

V

From the equipment nameplate.

2Load

Enter the load as

Switching converts the number you entered at the voltage the load needs.

A

Full-load amps from the nameplate. For three phase, the current in each line.

More detail (optional)Output within ±5% of the voltage the load needs, 60 Hz. Tap to change.
%

How far from the voltage the load needs an option may land. 5% is the default of the Federal Pacific selector. Check the load's allowed voltage range.

Closest to the voltage you asked for

0.75 kVA

16/32 V winding, single-phase, 240.0 V out (0.0%)

Output voltage
240.0 V (0.00%)
Direction
Boost, 15.4% change
Windings used
240 V common − 32 V series
Load current used
20 A
Required VA per unit
738 VA
Max load current at 0.75 kVA
20.3 A
Max source current at 0.75 kVA
23.4 A
Source current at your load
23.1 A

Load on the 240 V winding. The 32 V winding subtracts from it, and the line connects across the combination (240 − 32 = 208 V rated). Terminal marks differ by maker, so wire it from the diagram that comes with the unit.

The unit does not isolate the load from the supply, and it does not regulate. If the supply moves 3%, the output moves about 3%.

This uses the example 208 V supply, 240 V load, 20 A. Enter your own values to get your result.

4 options within ±5%

Select one to see its details above.

Overcurrent protection, NEC 2023 450.4(A)

Rated input current at 0.75 kVA
23.4 A
Limit, 125% of that
29.3 A
Next standard rating (240.6)
Fuse 30 A, breaker 30 A

One device in series with each ungrounded input conductor. None goes in series with the common winding between its two ends.

At 9 A or more, the next higher standard rating is permitted. Use the unit's rated input current, not your load, since the rule is written on the rated value.

Other NEC 2023 points

A transformer field-connected as an autotransformer shall be identified for use at elevated voltage (450.4(B)). Check the unit's marking.

208 V to 240 V, and 240 V to 208 V, is named in the exceptions to 210.9 and 215.11. Those exceptions allow the circuit without a grounded conductor connected to a grounded conductor of the supplying system. Confirm with your inspector.

Share this result

https://kvcalc.com/tools/buck-boost-transformer-calculator/

✉ Email
Post to social

The link carries the full calculation, so anyone opening it lands on the same inputs and the same result.

How to size a buck-boost transformer

  1. Measure the supply voltage and read the voltage the load needs from its nameplate.
  2. Get the load current at the load voltage. From kVA, single phase is kVA × 1000 ÷ volts. Three phase is kVA × 1000 ÷ (1.732 × line-to-line volts).
  3. Pick a connection whose output is inside the load’s voltage range. The output is the supply voltage times a ratio set by the windings.
  4. Required VA is the load amps times the volts on the series winding. When the load sits on the common winding, scale that by output volts ÷ supply volts.
  5. Round up to the next unit size. This tool uses 50 VA, 100 VA, 150 VA, 250 VA, 500 VA, 750 VA, 1 kVA, 1.5 kVA, 2 kVA, 3 kVA, 5 kVA, 7.5 kVA.

Example: a single-phase load of 20 A on a 208 V supply that needs 240 V. With a 16/32 V unit, the load on the 240 V winding and the 208 V line across 240 V less 32 V gives 240.0 V. The unit must supply 20 × 36.9 = 738 VA, so a 0.75 kVA unit. At that size it can carry 20.3 A on the load and 23.4 A on the supply. Adding the 32 V winding to the line instead gives 235.7 V and needs 20 × 32 = 640 VA, which is also a 0.75 kVA unit.

Buck-boost transformer sizing chart: 208 V to 240 V

Single phase, 12/24 V and 16/32 V units, within 5% of 240 V. The first column is the option closest to 240 V. The second is the smallest unit that gets within 5%. Both are calculated from the rules above.

Load (A at 240 V)Closest voltageUnitSmallest unitUnit
5240.0 V0.25 kVA231.1 V0.15 kVA
10240.0 V0.5 kVA228.8 V0.25 kVA
15240.0 V0.75 kVA235.7 V0.5 kVA
20240.0 V0.75 kVA228.8 V0.5 kVA
25240.0 V1 kVA231.1 V0.75 kVA
30240.0 V1.5 kVA228.8 V0.75 kVA
40240.0 V1.5 kVA228.8 V1 kVA

Where a buck-boost transformer fits

A buck-boost transformer corrects a supply that is a modest step off the voltage a load needs, for example 208 V to 240 V, or 240 V down to 208 V. Because only the series winding carries the difference, the unit is small next to a full isolation transformer. If you need isolation, a different phase count, a neutral on a delta system or a large voltage change, use a standard transformer and size it with the transformer sizing calculator.

What the result is not. The tool does not return a manufacturer part number and does not give wiring terminal numbers, which differ between makers. It does not isolate, regulate or derate for altitude and ambient temperature. It covers 60 Hz, 120 × 240 V primaries with 12/24 V and 16/32 V secondaries only. Wire from the diagram that ships with the unit and have the install checked by a qualified person.

Sources.Eaton buck-boost design guide DG009004EN, selection tables 19.4-2 to 19.4-11;Federal Pacific Buck-Boost Transformer Calculator/Selector;Schneider Electric FAQ FA91925: selecting a Buck & Boost transformer, 208 V to 240 V. Overcurrent limits follow NFPA 70 (NEC) 2023, 450.4. KVCalc is not affiliated with these companies. Results are an aid for checking a design, not a substitute for an engineer’s review. Checked on 2026-10-09.

Questions people actually ask

How do I size a buck-boost transformer?

Find the voltage you have and the voltage the load needs, then the load current at the load voltage. Pick a connection that lands within the load's allowed voltage range, and multiply the load amps by the volts on the series winding. That is the VA the unit must supply. Round up to the next unit size. For 20 A at 208 V to 240 V, the 16/32 V unit connected to give 240.0 V needs 20 x 36.9 = 738 VA, so a 0.75 kVA unit.

How do I go from 208 V to 240 V with a buck-boost transformer?

Boost it. A 120 x 240 V primary with a 16/32 V secondary can be wired in two ways that suit 208 V to 240 V. Adding the 32 V winding to the 208 V line gives about 235.7 V (-1.8%). Putting the load on the 240 V winding and the 208 V line across it with the 32 V winding subtracted gives 240.0 V. The second needs a slightly larger unit. This tool lists both, with the unit size for your load.

Why does the calculator offer more than one answer?

A unit can be wired several ways, and each gives a slightly different output voltage and needs a different kVA for the same load. The closest voltage is listed first. If your equipment tolerates a few percent, a lower voltage may fit on a smaller, cheaper unit. The tolerance under More detail sets how far from the voltage you asked for an option may land. It starts at 5%, the default used by the Federal Pacific selector.

Does the load amps or the source amps set the size?

The load amps, through the series winding. The unit only carries the voltage it adds or removes, so a buck-boost unit is much smaller than a transformer for the same load. The source current is different from the load current, because power is the same on both sides: a boost draws more current than it delivers. The result shows both.

What size fuse or breaker does a buck-boost transformer need?

NEC 2023 450.4(A) limits the overcurrent device on the input to 125% of the rated input current, and allows the next higher standard rating when that is not a standard size and the input is 9 A or more. Below 9 A the limit is 167% and the rating is not rounded up. The 0.75 kVA unit in the example has a rated input of 23.4 A, so the limit is 29.3 A and the next standard rating is 30 A. The device goes in series with each ungrounded input conductor, never across the common winding. The tool also shows this for the unit you pick.

Can I use a buck-boost transformer on a three-phase system?

Yes, on the same number of phases it serves. Two units make an open delta, which gives three wires and no neutral. Three units make a wye and need a four-wire source with the neutral tied to the common point. The calculator sizes each unit for the line current. It does not change single phase to three phase, and it does not make a neutral on a delta system.

Is a buck-boost transformer isolated?

No. It is wired as an autotransformer, so the load stays connected to the supply, and if the supply voltage moves, the output moves with it by about the same percentage. It does not regulate. Eaton lists limits for 60 Hz only and says not to use these units on control circuits or on an unstable line voltage.

Does this work for Square D, Eaton, Hammond, Acme or Federal Pacific units?

It works from the common ratings of 120 x 240 V primaries with 12/24 V or 16/32 V secondaries, which Eaton and Federal Pacific publish. The tool applies the winding voltage and VA relations in those guides and was checked against the Eaton tables and the Federal Pacific selector for 208 V to 240 V. Not every cell of the Eaton tables is reproduced, so confirm the final unit against the manufacturer table. It does not return a manufacturer part number, and kVA sizes follow the Eaton list, so another maker may offer different ones. KVCalc has no connection to any of these companies. Terminal marks and wiring diagrams differ between makers, so wire from the diagram that comes with your unit. Schneider Electric describes the same method for 208 V to 240 V: 32 V times the load current gives the VA.

What does the calculator not cover?

It does not cover 240 x 480 V units or any 480 V class system, so 480 V, 480Y/277 V and 600 V are outside it. It does not derate for altitude or ambient temperature, which Eaton does for high altitude and high ambient. It does not cover loads above the largest listed unit, 7.5 kVA. It does not check the load's allowed voltage range, motor starting current, or whether the equipment is rated to run from a non-isolated source.

Does the NEC allow a buck-boost transformer on a branch circuit?

NEC 2023 210.9 and 215.11 say branch circuits and feeders shall not be derived from an autotransformer unless the circuit (210.9) or system (215.11) supplied has a grounded conductor that is electrically connected to a grounded conductor of the system supplying the autotransformer. Exception No. 1 allows an autotransformer without that connection when transforming from a nominal 208 V to a nominal 240 V supply, or from 240 V to 208 V. Exception No. 2 covers 480 V and 600 V in industrial occupancies with qualified maintenance and supervision. For any other pair, check with your inspector. 450.4(B) also says a transformer field-connected as an autotransformer shall be identified for use at elevated voltage.

Related calculators