Voltage drop · DC, single or three phase · Cu / Al
Voltage Drop Calculator
Enter the load, one-way length and conductor to see volts lost, the smallest passing wire size and the longest run.
By Allen Tan · Updated · How results are sourced
1Supply and load
Voltage at the supply end.
Actual load current, not the breaker rating. kVA is converted at the source voltage.
Measure one way along the run, not there and back. The tool doubles it for single phase.
2Conductors
Areas from NEC Chapter 9, Table 8. Aluminum starts at 12 AWG.
More detail (optional)Target 3% drop, 1 set per phase. Tap to change.
Sets above 1 need 1/0 AWG or larger under NEC 310.10(H).
The 3% figure is an Informational Note recommendation, not a code limit. Feeders and branches are commonly designed to 3%, 5% total.
Over 3% target
6.58 % drop
7.9 V lost on 12 AWG copper, 112.1 V at the load
- Voltage drop
- 7.9 V (6.58%)
- Voltage at the load
- 112.1 V
- Load current used
- 20 A
- Ampacity of 12 AWG copper
- 20 A at 60 °C, load 20 A
- Longest run at 3%
- 46 ft one way on 12 AWG copper
- Formula
- 2 × K × I × L / CM
- Smallest size meeting 3%
- 8 AWG (2.6%)
This uses the example 120 V, 20 A, 100 ft, 12 AWG copper. Enter your own values to get your result.
What the result is not
An estimate at 75 °C with no reactance, no temperature correction and power factor 1.0. Long runs and larger sizes read slightly low. Ampacity is checked against NEC Table 310.16 at 30 °C ambient with no more than three current-carrying conductors, with no ambient or conductor-count correction. It does not check protection, terminals or the overcurrent device limit in 240.4(D). Confirm the conductor with the secondary conductor sizing calculator.
Share this result
https://kvcalc.com/tools/voltage-drop-calculator/
The link carries the full calculation, so anyone opening it lands on the same inputs and the same result.
Enter the load, the one-way length and the conductor. See the volts lost, the percentage, the smallest wire size that meets your target and the maximum distance that size can run.
How to use this voltage drop calculator
The tool solves three questions from the same inputs: how much voltage is lost, which wire size is enough, and how far a given wire can run.
- Pick the system: DC, single-phase or three-phase, and copper or aluminum.
- Enter the supply voltage. For three-phase, use the line-to-line voltage. For DC, use the battery or supply voltage, such as 12, 24 or 48.
- Enter the load as amps, or as kVA (kW for DC). Use the actual load current, not the breaker rating.
- Enter the one-way length in feet, measured along the run. The tool doubles it for you, so do not enter the round-trip length.
- Choose the wire size and the drop target. Read the volts lost, the percentage, the voltage at the load, the smallest size that meets your target and the longest run that size allows. If the size you picked is too small for the current, the tool says so and suggests a size that carries the load.
Worked example: 120 V, 20 A, 100 ft on 12 AWG copper
A 20 A load at the end of 100 ft of 12 AWG copper (6,530 circular mils). Single phase counts both directions, so the length factor is 2.
| Step | Result |
|---|---|
| Drop, 2 x 12.9 x 20 x 100 / 6,530 | 7.90 V |
| Percentage, 7.90 / 120 | 6.58% |
| At the load | 112.1 V |
| Against the 3% target | Over — about twice the recommended drop |
| Smallest copper size meeting 3% | 8 AWG (2.60%) |
| Longest 12 AWG run at 3% | 45.6 ft |
The 3% figure is an Informational Note recommendation, not a code limit. The tool still flags this run because long 120 V circuits are where equipment feels the loss first.
Worked example: 12 V DC, 10 A, 20 ft on 10 AWG copper
DC uses the same factor of 2 as single-phase AC because current travels out and back.
| Step | Result |
|---|---|
| Drop | 0.50 V |
| Percentage | 4.14% |
| At the load | 11.5 V |
| Smallest copper size meeting 3% | 8 AWG (2.60%) |
| Longest 10 AWG run at 3% | 14.5 ft |
How voltage drop works
Voltage drop is the voltage lost along a conductor between the supply and the load. The load sees the supply voltage minus the drop, so a long or heavily loaded run can leave equipment short of voltage.
It comes from Ohm's law. Every conductor has resistance, and current flowing through that resistance loses voltage: V = I x R. The tool works out R from the conductor material, the size and the length.
Four things set the size of the drop:
- Material: aluminum has about 64% more resistance than copper for the same size.
- Wire size: a larger conductor has more area and less resistance.
- Length: resistance grows with the length of the run.
- Current: the drop is proportional to the load current.
The tool uses the K-factor method from NEC Chapter 9, Table 8 areas: single-phase and DC drop is 2 x K x I x L / CM, and three-phase drop is 1.732 x K x I x L / CM. K is 12.9 for copper and 21.2 for aluminum at 75 °C. Divide the drop by the supply voltage to get the percentage. Resistance rises with temperature, and this method ignores reactance, so it is an estimate. See the warning box below for what it leaves out.
What the NEC asks for
NEC 2023 210.19(A) Informational Note No. 4 recommends keeping branch-circuit drop to 3%, and 215.2(A)(1) Informational Note No. 2 recommends 5% total from service to the farthest outlet. Conductor areas come from Chapter 9, Table 8. Section numbers were checked against the 2023 edition; check the edition your jurisdiction has adopted. This tool gives you the calculation, not a pass/fail against the code — there is no code limit to pass.
What the result is not. An estimate at 75 °C with no reactance, no temperature correction and power factor 1.0 — long runs and larger sizes read slightly low. It does not check protection, terminal ratings or the overcurrent device limit in 240.4(D). Do not use a passing drop result to justify an undersized conductor.
After choosing a conductor size, check that the conductors fit your conduit with the conduit fill calculator.
Source.Conductor areas: NEC 2023 Chapter 9, Table 8. Recommendation text: NEC 2023 210.19(A) Informational Note No. 4 and 215.2(A)(1) Informational Note No. 2. The K-factor formula is the standard resistance method in electrician references; K = 12.9 (Cu) / 21.2 (Al) ohm-cmil/ft at 75 °C. Ampacity: NEC 2023 Table 310.16 (60 °C and 75 °C copper and aluminum columns); column selection follows NEC 110.14(C)(1) as summarized by secondary sources.
Disclaimer. Conductor areas from NEC 2023 Chapter 9, Table 8; 3%/5% figures are Informational Note recommendations, not code limits. An estimate for sizing checks, not engineering advice. Not engineering advice and not a substitute for the code text. Verify against the edition adopted in your jurisdiction and with your Authority Having Jurisdiction — protection decisions affect life safety.
Questions people actually ask
What is voltage drop?
Current pushing through conductor resistance uses up some of the voltage along the run, so the load sees less than the supply. Longer runs, higher current and smaller conductors all increase it. A 120 V circuit losing 7.9 V delivers about 112 V at the far end, which is why long 120 V runs are the first place drop shows up.
How do you calculate voltage drop?
Single-phase: 2 x K x I x L divided by CM. Three-phase: 1.732 x K x I x L divided by CM. I is the load current in amps, L is the one-way length in feet, CM is the conductor area in circular mils from NEC Chapter 9, Table 8, and K is 12.9 for copper or 21.2 for aluminum at 75 °C. Divide the drop by the source voltage for the percentage.
Does the NEC require voltage drop to stay under 3%?
No. The 3% figure for a branch circuit or feeder, and 5% total, comes from Informational Notes (NEC 2023 210.19(A) Informational Note No. 4 and 215.2(A)(1) Informational Note No. 2). Informational Notes are recommendations, not enforceable rules by themselves, but some project specifications and local amendments adopt them, so check yours. Motors, heaters and electronics feel the loss either way. This tool defaults the target to 3% and lets you change it.
Do I enter the length one way or there and back?
One way, measured along the run. The tool doubles it for single phase (current travels out and back) and uses 1.732 for three phase. Entering the round-trip length double-counts and oversizes the wire by one or two sizes.
How much worse is aluminum than copper?
About 64% more drop for the same size and length (21.2 divided by 12.9). A 12 AWG aluminum run drops what a 12 AWG copper run drops times 1.64. Going up one or two sizes in aluminum usually brings it back in line with the copper answer.
The drop is over target. What are my options besides larger wire?
Shorten the run, add a parallel set per phase, raise the supply voltage, or move the load closer to the source. Parallel sets multiply the effective area, but each set must be 1/0 AWG or larger under NEC 310.10(H). Raising voltage helps twice: the same power draws less current and the same volts lost are a smaller percentage.
Does this check ampacity or breaker size?
It checks ampacity against NEC Table 310.16 for the size it suggests, so it never suggests a conductor that cannot carry the load. It assumes 30 °C ambient and no more than three current-carrying conductors, and it does not correct for heat or conductor count. It does not check the overcurrent device limits in 240.4(D) or terminal ratings. Confirm the conductor with the secondary conductor calculator and check the cable run effect on faults with the fault current calculator.
How do you calculate DC voltage drop?
Multiply 2 by K, the load current, the one-way length and divide by the conductor circular mils: VD = 2 x K x I x L / CM. K is 12.9 for copper and 21.2 for aluminum at 75 °C. Pick DC in the tool and enter the one-way length. For a 12 V system, even a 3% drop is only 0.36 V, so short runs need heavy wire.
How far can I run a wire before the voltage drop is too high?
Solve the same formula for length: L = target% x V x CM / (100 x 2 x K x I) for single-phase and DC, with 1.732 in place of 2 for three-phase. The tool does this for you and shows the longest one-way run for the size you picked. More parallel sets multiply the allowed length.
How do I find the wire size for a given voltage drop?
Enter the load, voltage and one-way length, then read the smallest size that meets your target. The tool tries each size from 14 AWG to 2000 kcmil with your material and parallel sets, and only suggests sizes that also carry the load current. Ampacity is checked at 30 °C ambient with no more than three current-carrying conductors and no heat or count correction; confirm the conductor with the secondary conductor sizing calculator for your actual conditions.
Why does this result differ from other voltage drop calculators?
Different calculators use different conductor data. This one uses the K-factor method (12.9 copper / 21.2 aluminum at 75 °C), a resistance-only estimate that ignores reactance. Some calculators use resistance at 20 °C, which is about 18% lower, so they read lower. Others use NEC Chapter 9, Table 9 effective impedance, which combines AC resistance and reactance at your power factor. On small wire near unity power factor the methods agree within a few percent. On large conductors with motor loads, Table 9 can read much higher. Match the method your specification names.
Related calculators
Secondary Conductor Sizing Calculator (NEC 310.16)
Ampacity with ambient correction and terminal limits.
OpenAvailable Fault Current Calculator
Fault current from transformer %Z, then through each cable run.
OpenTransformer Sizing Calculator