Transformer Impedance: IS 1180 Minimum Values

By · Updated · How results are sourced

Transformer Impedance Calculator

This lookup returns the minimum short-circuit impedance for a listed transformer rating, phase and voltage class in the IS 1180 tables cited on this page. It covers the listed single-phase and three-phase ratings up to and including the 11 kV class. The result is a table minimum; it does not establish the actual impedance of an individual transformer, provide a value for an unlisted rating or voltage class, or establish compliance with all applicable requirements.

1Transformer details

Enter a positive kVA rating and select the phase and voltage class.

Phase

Result

Enter a positive kVA rating and select the phase and voltage class.

What the IS 1180 Minimum Means

A minimum is a lower limit for the relevant table entry. It is not a measured value for an individual transformer, a typical value or a band of acceptable values. A lookup result therefore answers which minimum is listed for that rating and phase within the voltage class covered here.

The cited tables do not supply the test result for a particular unit. Temperature, tap position and test conditions are not evaluated by this lookup, so the displayed minimum must not be presented as the transformer's measured impedance under operating conditions. The lookup also does not assess the other requirements that may apply to a procurement or installation.

Three-Phase Minimum Impedance: Table 3

Table 3 covers the listed three-phase ratings of 16, 25, 63, 100, 160 and 200 kVA, up to and including the 11 kV class. The minimum short-circuit impedance is 4.5% at each of these ratings. Each rating is a separate listed entry; the entries do not establish values for intermediate capacities.

The larger three-phase ratings listed on this page belong to Table 6. Single-phase ratings belong to Table 9, even where the numerical kVA rating also appears in Table 3. Phase selection is therefore part of the lookup, rather than an interchangeable description of the same result.

Table 3 — Three-phase transformers — Up to 11 kV class
Rated power (kVA)Minimum short-circuit impedance (%)
164.50
254.50
634.50
1004.50
1604.50
2004.50

IS 1180 (Part 1) : 2014; Amendment No. 4, March 2021; Table 3. Version checked: 6 November 2026.

Three-Phase Minimum Impedance: Table 6

Table 6 covers the listed larger three-phase ratings up to and including the 11 kV class. The minimum is 4.50% for 250, 315, 400, 500 and 630 kVA; 5.00% for 800, 1000 and 1250 kVA; and 6.25% for 1600, 2000 and 2500 kVA. These values apply to the individual listed ratings.

Table 6 does not extend the smaller three-phase entries in Table 3 into a continuous capacity curve. It also does not supply single-phase values or values for voltage classes above those covered by the cited tables. An unlisted rating has no result in this lookup.

Table 6 — Three-phase transformers — Up to 11 kV class
Rated power (kVA)Minimum short-circuit impedance (%)
2504.50
3154.50
4004.50
5004.50
6304.50
8005.00
10005.00
12505.00
16006.25
20006.25
25006.25

IS 1180 (Part 1) : 2014; Amendment No. 4, March 2021; Table 6. Version checked: 6 November 2026.

Single-Phase Minimum Impedance: Table 9

Table 9 covers the listed single-phase ratings up to and including the 11 kV class. The minimum is 2.50% for 5 kVA and 4.00% for 10, 16, 25, 50, 75 and 100 kVA. These are single-phase entries; their values must not be transferred to a three-phase transformer with the same kVA rating.

Tables 3 and 6 provide the three-phase entries used on this page. A capacity appearing in Table 9 does not create a corresponding entry in either three-phase table. The selected phase and the exact listed capacity must both match.

Table 9 — Single-phase transformers — Up to 11 kV class
Rated power (kVA)Minimum short-circuit impedance (%)
52.50
104.00
164.00
254.00
504.00
754.00
1004.00

IS 1180 (Part 1) : 2014; Amendment No. 4, March 2021; Table 9. Version checked: 6 November 2026.

Unlisted Ratings and Voltage Classes

An unlisted capacity within the covered capacities is still an unlisted entry. For example, a three-phase 50 kVA rating has no value in the tables used here, even though a single-phase entry exists at that capacity. The lookup does not interpolate between listed ratings or substitute the value from another phase.

A rating beyond the largest listed entry also has no result: the three-phase entries stop at 2500 kVA and the single-phase entries at 100 kVA. A rating below the smallest listed entry has no result either: the three-phase entries start at 16 kVA and the single-phase entries at 5 kVA. This page neither extrapolates nor interpolates a minimum beyond the listed entries.

The tables cited on this page do not list impedance values for the 22 kV or 33 kV voltage classes. No minimum is supplied here for a voltage class above 11 kV, or for a class that has not been identified. This limitation of the lookup does not establish whether another applicable specification provides a requirement; the relevant DISCOM (distribution company) or procurement specification and the manufacturer's confirmation are needed to resolve that question.

Percentage Impedance and Fault Current

Percentage impedance expresses impedance relative to a selected base: %Z = 100 × |Z| / Z_base, with Z_base = V_base² / S_base. The impedance and base quantities must refer to the same transformer side. For three-phase calculations, the base uses line-to-line voltage and total three-phase apparent power; for single-phase calculations, it uses winding voltage and single-phase apparent power. With voltage in volts and apparent power in volt-amperes, the resulting base impedance is in ohms. Primary-side and secondary-side quantities, or line and phase bases, must not be mixed.

The simplified current relationship is I_sc = I_FLA × (100 / %Z). On the primary-side basis used here, I_FLA = S / (√3 × V) for three-phase equipment and I_FLA = S / V for single-phase equipment, using primary-side rated voltage and rated apparent power. Voltage in volts and apparent power in volt-amperes give current in amperes. With the rated current held constant, a lower percentage impedance produces a higher calculated fault current in this relationship. A table minimum used as the input gives an estimate under these assumptions, not a measured fault current.

This calculation assumes an infinite source and neglects source impedance and cable impedance. It also neglects the resistance component and impedance angle, excludes motor contribution and does not give an asymmetrical peak current. The expression is not applicable where percentage impedance varies with tap position. These relationships follow an algebraic derivation and a dimensional check, and are consistent with the implementation already used on this site under the stated assumptions.

The site's available fault current calculator has an upper limit for secondary voltage. Its supported secondary-voltage inputs must be checked before use; a successful impedance lookup does not establish that a separate fault-current calculation is within that tool's supported inputs.

Sources, Edition and Table References

The edition used for this lookup is IS 1180 (Part 1) : 2014, with Amendments 1 to 4, the most recent dated March 2021. The impedance entries on this page are taken from Tables 3 and 6 for three-phase ratings and Table 9 for single-phase ratings.

Each reference below was opened on 6 November 2026. The BIS product manual records “No. of Amendments : 4”. The table references support the lookup values; the algebraic relationships above are described separately with their assumptions and are not attributed to any standard text.

Frequently Asked Questions

Answers to common questions about the IS 1180 minimum impedance entries used on this page.

How do US DOE impedance limits differ from IS 1180 minimum values?

The US DOE limits used on this site give lower and upper bounds for identifying a special-impedance transformer, whereas the IS 1180 entries used here give minimum values. The capacity entries differ, so the US DOE lookup must not be treated as a direct substitute for these tables.

Why is 50 kVA not listed for a three-phase transformer?

The three-phase tables used here do not include a 50 kVA entry. The single-phase entry at that capacity does not supply a three-phase minimum, and this lookup does not infer one.

What should I use for a 22 kV or 33 kV transformer?

The tables cited on this page do not list impedance values for either voltage class, so this lookup supplies no minimum. The applicable DISCOM or procurement specification and the manufacturer’s confirmation are needed; whether another specification supplies a requirement has not been established here.

Are the impedance values in IS 1180 and IEC 60076-5 the same?

No; the impedance values differ and must not be used interchangeably. This page supplies the cited IS 1180 table entries, without a numerical comparison against IEC 60076-5.

Is the listed minimum the actual impedance of my transformer?

Not necessarily. It is the minimum for the listed table entry, not the measured impedance of an individual transformer, and a particular unit may differ. This lookup does not evaluate the unit’s temperature, tap position or test conditions.

Can I interpolate an impedance value for an unlisted kVA rating?

No interpolated value is provided or supported by this table lookup. An unlisted rating requires confirmation against the applicable procurement specification and with the manufacturer.

What happens above 2500 kVA three-phase or 100 kVA single-phase?

This lookup returns no minimum above those listed capacities. It does not extrapolate the final entry or establish what another applicable specification requires.

Can I use the minimum impedance to estimate fault current?

Yes, as the input to the simplified relationship I_sc = I_FLA × (100 / %Z), provided all of its stated assumptions apply. The result excludes source and cable impedance, resistance and impedance-angle effects, motor contribution and asymmetrical peak current, and the relationship does not apply where percentage impedance varies with tap position. A successful lookup does not establish that a separate fault-current calculation is within the supported inputs of the fault-current tool on this site.

Which IS 1180 edition and amendment does this lookup use?

It uses IS 1180 (Part 1) : 2014, with Amendments 1 to 4, the most recent dated March 2021. The lookup draws its impedance entries from Tables 3, 6 and 9, up to and including the 11 kV class.

How do I choose the kVA rating before checking impedance?

Rating selection is a separate step; this impedance lookup starts with a selected kVA rating. The site’s transformer sizing calculator and kVA, kW and amps calculator are separate tools, and the resulting selected rating still needs an exact phase and capacity match in the tables used here.