PVC conduit fill · Schedule 40 / Schedule 80 · THHN / XHHW
PVC Conduit Fill Chart (Schedule 40 & Schedule 80)
Schedule 40 and Schedule 80 side by side for THHN and XHHW, or check your own mix with the calculator below.
Quick answer. At the same trade size, Schedule 80 has a smaller interior area than Schedule 40 (0.832 sq in versus 0.688 sq in at 1 in), so the same conductors fill more of it. Read the Schedule 40 / Schedule 80 pair in the chart for your trade size.
Jump to: THHN chart, XHHW chart, Schedule 40 vs 80 areas, Worked example, Calculator, Next steps, FAQ.
By Allen Tan · Updated · How results are sourced
1Conductors
Group 1
Count the equipment grounding conductor (EGC) toward fill. Add it as its own conductor group with the correct size and quantity; the calculator does not add it automatically. Choose the insulated type here for an insulated EGC. A bare EGC is not supported because bare conductor areas (Chapter 9, Table 8) are not in this tool.
2Raceway and mode
Pick a size to check a specific run.
Nipple (optional)Leave off unless this section qualifies as a nipple. Tap to change.
Pass at 40% limit
7.85 % fill
0.0399 sq in of conductors in 3/4 in PVC Schedule 40
- Total conductor area
- 0.0399 sq in
- Conduit interior area
- 0.5080 sq in
- Allowable area
- 0.2032 sq in at 40%
- Area left under the limit
- 0.1633 sq in
- Fill
- 7.85%
- Limit applied
- 40% (3 conductors)
- Smallest passing size
- 1/2 in PVC Schedule 40
KVCalc · NEC 2023 Table 4 (Arts. 352 and 353, PVC Schedule 40) · p. 70-719 · checked 2026-10-17
This uses the example 3 x 12 AWG THHN in 3/4 in PVC Schedule 40. Enter your own values to get your result.
Share this result
https://kvcalc.com/tools/pvc-conduit-fill-chart/
The link carries the full calculation, so anyone opening it lands on the same inputs and the same result.
Maximum same-size count
12 AWG THHN in 3/4 in PVC Schedule 40: 15 (strict 15).
PVC conduit fill chart: THHN, Schedule 40 / Schedule 80
Each cell: Schedule 40 count / Schedule 80 count. Find your wire size in the left column and your trade size across the top.
| THHN wire size | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in | 2-1/2 in | 3 in | 3-1/2 in | 4 in | 5 in | 6 in |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 11 / 9* | 21* / 17* | 34 / 28 | 60* / 51 | 82* / 70 | 135 / 118 | 193 / 170* | 299 / 265 | 401 / 358 | 517 / 464 | 815* / 736 | 1178 / 1055 |
| 12 AWG | 8 / 6 | 15 / 12 | 25 / 20 | 43 / 37 | 59 / 51 | 99* / 86 | 141 / 124* | 218 / 193 | 293* / 261 | 377 / 338 | 594 / 537* | 859 / 770* |
| 10 AWG | 5 / 4 | 9 / 7 | 15 / 13 | 27 / 23 | 37 / 32 | 62 / 54 | 89 / 78 | 137 / 122 | 184 / 164 | 238* / 213 | 374 / 338 | 541 / 485 |
| 8 AWG | 3 / 2* | 5 / 4 | 9 / 7 | 16* / 13 | 21 / 18 | 36* / 31 | 51 / 45 | 79 / 70 | 106 / 95* | 137 / 123 | 216* / 195 | 312 / 279 |
| 6 AWG | 1 / 1 | 4 / 3 | 6 / 5 | 11 / 9 | 15 / 13 | 26* / 22 | 37 / 32 | 57 / 51* | 77* / 68 | 99 / 89* | 156* / 141* | 225 / 202* |
| 4 AWG | 1 / 1 | 2* / 1 | 4 / 3 | 7 / 6 | 9 / 8 | 16* / 14* | 22 / 20* | 35 / 31 | 47 / 42 | 61* / 54 | 96* / 86 | 138 / 124 |
| 3 AWG | 1 / 1 | 1 / 1 | 3 / 3* | 6* / 5 | 8 / 7 | 13 / 12* | 19 / 17* | 30* / 26 | 40 / 35 | 51 / 46 | 81 / 73 | 117 / 105 |
| 2 AWG | 1 / 1* | 1 / 1 | 3* / 2* | 5 / 4 | 7* / 6* | 11 / 10* | 16 / 14 | 25 / 22 | 33 / 30 | 43 / 39* | 68 / 61 | 98 / 88 |
| 1 AWG | 1* / 0 | 1 / 1 | 1 / 1 | 3 / 3 | 5 / 4 | 8 / 7 | 12 / 10 | 18 / 16 | 25* / 22 | 32 / 29* | 50 / 45 | 73 / 65 |
| 1/0 AWG | 1* / 0 | 1 / 1 | 1 / 1 | 3 / 2 | 4 / 3 | 7 / 6 | 10 / 9* | 15 / 14* | 21* / 18 | 27 / 24 | 42 / 38 | 61 / 55 |
| 2/0 AWG | 0 / 0 | 1 / 1* | 1 / 1 | 2 / 1 | 3 / 3 | 6* / 5 | 8 / 7 | 13 / 11 | 17 / 15 | 22 / 20 | 35 / 32 | 51 / 46 |
| 3/0 AWG | 0 / 0 | 1 / 1* | 1 / 1 | 1 / 1 | 3* / 2* | 5* / 4 | 7 / 6 | 11* / 9 | 14 / 13* | 18 / 17* | 29 / 26 | 42 / 38 |
| 4/0 AWG | 0 / 0 | 1* / 0 | 1 / 1 | 1 / 1 | 2* / 1 | 4 / 3 | 6* / 5 | 9* / 8* | 12 / 10 | 15 / 14* | 24 / 22 | 35 / 31 |
| 250 kcmil | 0 / 0 | 0 / 0 | 1 / 1* | 1 / 1 | 1 / 1 | 3 / 3* | 4 / 4 | 7 / 6 | 10* / 8 | 12 / 11 | 20* / 18* | 28 / 25 |
| 350 kcmil | 0 / 0 | 0 / 0 | 1* / 0 | 1 / 1 | 1 / 1 | 2* / 1 | 3 / 3 | 5 / 5* | 7 / 6 | 9 / 8 | 15 / 13 | 21 / 19 |
| 500 kcmil | 0 / 0 | 0 / 0 | 0 / 0 | 1 / 1* | 1 / 1 | 1 / 1 | 2 / 2* | 4 / 3 | 5 / 5* | 7 / 6 | 11 / 10 | 16 / 14 |
| 750 kcmil | 0 / 0 | 0 / 0 | 0 / 0 | 0 / 0 | 1 / 1* | 1 / 1 | 1 / 1 | 2 / 2* | 3 / 3 | 4 / 4 | 7 / 7* | 11* / 9 |
PVC conduit fill chart: XHHW, Schedule 40 / Schedule 80
Each cell: Schedule 40 count / Schedule 80 count. Find your wire size in the left column and your trade size across the top.
| XHHW wire size | 1/2 in | 3/4 in | 1 in | 1-1/4 in | 1-1/2 in | 2 in | 2-1/2 in | 3 in | 3-1/2 in | 4 in | 5 in | 6 in |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 8 / 6 | 14 / 11 | 24* / 19 | 42* / 35 | 57 / 49 | 94 / 82 | 135 / 118 | 209 / 185 | 280 / 250 | 361 / 324* | 568 / 514* | 822 / 736 |
| 12 AWG | 6 / 4 | 11 / 9 | 18 / 15 | 32 / 27 | 44* / 38* | 72 / 63 | 103 / 91 | 160 / 142 | 215 / 192 | 277 / 248 | 436 / 394 | 631 / 565 |
| 10 AWG | 4 / 3 | 8 / 6 | 13 / 11 | 24* / 20 | 32 / 28 | 54 / 47 | 77 / 68* | 119 / 106 | 160 / 143 | 206 / 185 | 325 / 294* | 470 / 421 |
| 8 AWG | 2 / 1 | 4 / 3 | 7 / 6 | 13 / 11 | 18 / 15 | 30 / 26 | 43* / 37 | 66 / 59* | 89 / 79 | 115* / 103 | 181* / 163 | 261 / 234 |
| 6 AWG | 1 / 1 | 3 / 2 | 5 / 4 | 10* / 8 | 13 / 11 | 22 / 19 | 32* / 28* | 49 / 43 | 66 / 59* | 85 / 76 | 134* / 121 | 193 / 173 |
| 4 AWG | 1 / 1 | 2* / 1 | 4 / 3 | 7 / 6 | 9 / 8 | 16 / 14 | 23 / 20 | 35 / 31 | 48* / 42 | 61 / 55 | 97 / 87 | 140 / 125 |
| 3 AWG | 1 / 1 | 1 / 1 | 3 / 3* | 6 / 5 | 8 / 7 | 13 / 12* | 19 / 17 | 30 / 26 | 40 / 36 | 52 / 47* | 82 / 74 | 118 / 106 |
| 2 AWG | 1 / 1 | 1 / 1 | 3* / 2* | 5 / 4 | 7* / 6* | 11 / 10 | 16 / 14 | 25 / 22 | 34* / 30 | 44* / 39 | 69* / 62 | 99 / 89 |
| 1 AWG | 1* / 0 | 1 / 1 | 1 / 1 | 3 / 3 | 5 / 4 | 8 / 7 | 12 / 10 | 19* / 16 | 25 / 22 | 32 / 29 | 51 / 46 | 74 / 66 |
| 1/0 AWG | 1* / 0 | 1 / 1 | 1 / 1 | 3 / 2 | 4 / 3 | 7 / 6 | 10 / 9 | 16* / 14 | 21 / 19 | 27 / 24 | 43 / 39 | 62 / 56 |
| 2/0 AWG | 0 / 0 | 1 / 1* | 1 / 1 | 2 / 1 | 3 / 3 | 6 / 5 | 8 / 7 | 13 / 11 | 17 / 16* | 23* / 20 | 36 / 32 | 52 / 46 |
| 3/0 AWG | 0 / 0 | 1 / 1* | 1 / 1 | 1 / 1 | 3 / 2 | 5* / 4 | 7 / 6 | 11 / 9 | 14 / 13 | 19 / 17 | 30* / 27 | 43 / 38 |
| 4/0 AWG | 0 / 0 | 1* / 0 | 1 / 1 | 1 / 1 | 2* / 1 | 4 / 3 | 6* / 5 | 9 / 8 | 12 / 11* | 15 / 14 | 24 / 22 | 35 / 32 |
| 250 kcmil | 0 / 0 | 0 / 0 | 1 / 1* | 1 / 1 | 1 / 1 | 3 / 3* | 5* / 4 | 7 / 6 | 10* / 9* | 13* / 11 | 20 / 18 | 29 / 26 |
| 350 kcmil | 0 / 0 | 0 / 0 | 1* / 0 | 1 / 1 | 1 / 1 | 2* / 1 | 3 / 3 | 5 / 5* | 7 / 6 | 9 / 8 | 15 / 14* | 22 / 20* |
| 500 kcmil | 0 / 0 | 0 / 0 | 0 / 0 | 1 / 1* | 1 / 1 | 1 / 1 | 2 / 2* | 4 / 3 | 5 / 5* | 7 / 6 | 11 / 10 | 16 / 14 |
| 750 kcmil | 0 / 0 | 0 / 0 | 0 / 0 | 0 / 0 | 1* / 1* | 1 / 1 | 1 / 1 | 2 / 2* | 3 / 3 | 4 / 4 | 7 / 6 | 11* / 9 |
* Note 7 raises this count above the strict area result. A fractional part of 0.8 or greater rounds up to the next whole conductor. The same Note 7 basis is used in the NEC Annex C tables.
These counts are computed from NEC 2023 Chapter 9 Table 1, Table 4 and Table 5. Table 5 has no material column, so copper and aluminum conductors share the same chart. The Table 5 values cover round concentric-lay-stranded and solid conductors; compact-stranded conductors (Table 5A) are not in this chart, so check those against the actual conductor dimensions. Each cell is the maximum count of one wire size and insulation at a time; for mixed wire sizes use the calculator above. Count the equipment grounding conductor in the total. This page covers PVC Schedule 40 and Schedule 80 only, not ENT, HDPE, FMC or other raceway types. Confirm the edition your jurisdiction has adopted with your AHJ.
PVC Schedule 40 vs Schedule 80: interior area by trade size
At the same trade size, Schedule 80 has a thicker wall and a smaller interior area than Schedule 40, so the same conductors give a higher fill percentage in Schedule 80. Areas below are the Table 4 interior areas.
| Trade size | Schedule 40 area (sq in) | Schedule 80 area (sq in) | Schedule 80 as % of Schedule 40 |
|---|---|---|---|
| 1/2 in | 0.285 | 0.217 | 76.1% |
| 3/4 in | 0.508 | 0.409 | 80.5% |
| 1 in | 0.832 | 0.688 | 82.7% |
| 1-1/4 in | 1.453 | 1.237 | 85.1% |
| 1-1/2 in | 1.986 | 1.711 | 86.2% |
| 2 in | 3.291 | 2.874 | 87.3% |
| 2-1/2 in | 4.695 | 4.119 | 87.7% |
| 3 in | 7.268 | 6.442 | 88.6% |
| 3-1/2 in | 9.737 | 8.688 | 89.2% |
| 4 in | 12.554 | 11.258 | 89.7% |
| 5 in | 19.761 | 17.855 | 90.4% |
| 6 in | 28.567 | 25.598 | 89.6% |
Worked example: 3 x 250 kcmil + 1 x 4 AWG XHHW in PVC
This example uses 3 x 250 kcmil XHHW plus 1 x 4 AWG XHHW, with the nipple option off and the grounding conductor already included in the count.
Smallest Schedule 40: 2 in (38.06% fill, 40% limit). Smallest Schedule 80: 2-1/2 in (30.41% fill, 40% limit).
The Schedule 80 minimum is at least as large as the Schedule 40 minimum at the same fill, because its interior area is smaller. For mixed wire sizes like this one, use the calculator rather than adding cells from different chart rows.
Next steps after checking PVC conduit fill
A passing fill result only says the conductors fit the raceway; it does not mean ampacity, voltage drop or protection are checked.
- Check secondary conductor ampacity: for transformer secondary conductors, check ampacity, correction factors and terminal limits.
- Check voltage drop for the conductor run: fill only checks space; voltage drop depends on length, current and conductor size.
- Review transformer sizing for this feeder: if you are sizing the transformer behind this feeder.
Source.NEC 2023 Chapter 9, Tables 1, 4 and 5. Values on this page are computed from the table areas, not copied from a third-party chart.
- KVCalc · NEC 2023 Table 1 · p. 70-715 · checked 2026-10-17
- KVCalc · NEC 2023 Table 4 (Arts. 352 and 353, PVC Schedule 40) · p. 70-719 · checked 2026-10-17
- KVCalc · NEC 2023 Table 4 (Art. 352, PVC Schedule 80) · p. 70-718 to 70-719 · checked 2026-10-17
- KVCalc · NEC 2023 Table 5 (THHN, THWN, THWN-2) · p. 70-721 to 70-722 · checked 2026-10-17
- KVCalc · NEC 2023 Table 5 (XHHW, XHHW-2) · p. 70-722 to 70-723 · checked 2026-10-17
What this does not check
- Area comparison only. It does not check ampacity, voltage drop or derating.
- No Chapter 9 Table 9 impedance, no sealoff 25 percent rule, no bend reduction, no 240.4(D).
- THHN (covers THWN and THWN-2) and XHHW (covers XHHW-2) only, copper and aluminum alike.
- Conduit types: EMT, RMC, PVC Schedule 40 and PVC Schedule 80. Other raceways are not included.
- The local authority having jurisdiction may enforce a different edition of the NEC.
Check the edition your jurisdiction has adopted.
Disclaimer. This calculator is a sizing and checking aid and is not engineering advice; confirm every result with a licensed professional and your AHJ. Conduit areas from NEC 2023 Chapter 9, Tables 1, 4 and 5. Not engineering advice and not a substitute for the code text. Verify against the edition adopted in your jurisdiction and with your Authority Having Jurisdiction — protection decisions affect life safety.
Questions people actually ask
What is the difference between PVC Schedule 40 and Schedule 80 for conduit fill?
Schedule 80 has thicker walls, so at the same trade size its interior area is smaller (0.832 sq in for PVC Schedule 40 versus 0.688 sq in for PVC Schedule 80 at 1 in). The same conductors therefore give a higher fill percentage in Schedule 80. At this size the Schedule 80 bore is 82.7% of Schedule 40. Read the count from the chart column that matches your raceway.
How many #12 THHN wires fit in 1 inch PVC conduit?
25 in PVC Schedule 40 and 20 in PVC Schedule 80 THHN #12 conductors in 1 inch PVC conduit. This assumes all conductors are the same size, nipple off, with no other conductors in the conduit. Include the equipment grounding conductor in the count.
How many #12 wires fit in 1/2-inch PVC Schedule 40?
8 THHN #12 conductors (8 by the strict area check). This assumes all conductors are the same size, nipple off, with no other conductors in the conduit. Include the equipment grounding conductor in the count.
How many #12 wires fit in 3/4-inch PVC Schedule 40?
15 THHN #12 conductors (15 by the strict area check). This assumes all conductors are the same size, nipple off, with no other conductors in the conduit. Include the equipment grounding conductor in the count.
How many #12 wires fit in 1/2-inch PVC Schedule 80?
6 THHN #12 conductors (6 by the strict area check). This assumes all conductors are the same size, nipple off, with no other conductors in the conduit. Include the equipment grounding conductor in the count.
How many wires can I fit in PVC conduit?
It depends on the schedule, trade size, insulation and wire size. Read the Schedule 40 / Schedule 80 pair for your trade size in the THHN chart or the XHHW chart. For mixed wire sizes, use the calculator with PVC Schedule 40 or PVC Schedule 80 selected.
Can I use an EMT chart for PVC conduit?
No. PVC has a different interior area than EMT at the same trade size, so the counts change. Use the charts on this page, or the EMT and RMC fill charts that match those raceways.
Do copper and aluminum conductors use the same fill chart?
Yes. Table 5 conductor areas have no material column, so the same chart applies to copper and aluminum. Still, check against the actual conductor dimensions: compact-stranded conductors use Table 5A areas, which this chart does not cover.
Do I count the ground wire?
Yes. Count the equipment grounding conductor toward fill. Add it as its own conductor group with the correct size and quantity; the calculator does not add it automatically.