Conduit fill · EMT / RMC / PVC Schedule 40 / PVC Schedule 80 · THHN / XHHW

Conduit Fill Chart & Calculator

Check conduit fill from your conductor groups and raceway, or jump straight to the EMT or RMC chart, or see the PVC Schedule 40 and Schedule 80 chart.

By · Updated · How results are sourced

1Conductors

Group 1

wires

Count the equipment grounding conductor (EGC) toward fill. Add it as its own conductor group with the correct size and quantity; the calculator does not add it automatically. Choose the insulated type here for an insulated EGC. A bare EGC is not supported because bare conductor areas (Chapter 9, Table 8) are not in this tool.

2Raceway and mode

Conduit type

EMT, RMC, PVC Schedule 40 and PVC Schedule 80 have different interior areas at the same trade size.

What to calculate

Auto searches the available trade sizes of the selected conduit type using the strict area check, without Note 7 rounding. If none passes, no minimum size is returned.

Pick a size to check a specific run.

Nipple (optional)Leave off unless this section qualifies as a nipple. Tap to change.
Qualifying nipple

Turn on only for a qualifying nipple installed between boxes, cabinets or similar enclosures and not exceeding 24 in (600 mm). The fill limit becomes 60%.

Pass at 40% limit

7.49 % fill

0.0399 sq in of conductors in 3/4 in EMT

Total conductor area
0.0399 sq in
Conduit interior area
0.5330 sq in
Allowable area
0.2132 sq in at 40%
Area left under the limit
0.1733 sq in
Fill
7.49%
Limit applied
40% (3 conductors)
Smallest passing size
1/2 in EMT

KVCalc · NEC 2023 Table 4 (Art. 358, EMT) · p. 70-716 · checked 2026-10-17

This uses the example 3 x 12 AWG THHN in 3/4 in EMT. Enter your own values to get your result.

Share this result

https://kvcalc.com/tools/conduit-fill-calculator/

✉ Email
Post to social

The link carries the full calculation, so anyone opening it lands on the same inputs and the same result.

Maximum same-size count

12 AWG THHN in 3/4 in EMT: 16 (strict 16).

Calculate conduit fill from your conductor groups and raceway type, then solve for the smallest passing conduit, the fill percentage of a selected conduit, or the maximum count of same-size conductors for a chosen conduit. Use the calculator above, or if you only need a wire count, go straight to the EMT or RMC conduit fill chart, or see the PVC Schedule 40 and Schedule 80 chart. The NEC limits fill to 53% of the conduit area for one conductor, 31% for two, 40% for three or more, and 60% for a qualifying nipple not exceeding 24 in (600 mm).

Conduit fill chart: maximum THHN conductors in EMT

EMT conduit fill chart. NEC 2023 Chapter 9 Tables 4/5 basis; Table 1 fill limits; areas checked against primary-source photographs.

Quick-reference table for THHN wire sizes (14 AWG to 2000 kcmil)

This is an electrical conduit fill chart for THHN conductors in EMT. Find your THHN wire size in the left column and your EMT trade size across the top. The cell shows the maximum same-size conductor count, including Note 7 rounding where marked, with the nipple option off and no other conductors in the conduit.

THHN wire size1/2 in EMT3/4 in EMT1 in EMT1-1/4 in EMT1-1/2 in EMT2 in EMT2-1/2 in EMT3 in EMT3-1/2 in EMT4 in EMT5 in EMT‡6 in EMT‡
14 AWG1222*356184*1382413644766088331202
12 AWG91626*45*61101*176266347443608*877*
10 AWG51016283863111167219*279383552
8 AWG36*91622366496126161221*318
6 AWG2*47*12*1626466991116159230
4 AWG124710*162843*567198141
3 AWG11368132436476083120*
2 AWG113*5711203040*51*70*100
1 AWG1114*58152229375174
1/0 AWG1*11347121925*32*4363*
2/0 AWG0112361016*20263652
3/0 AWG01113581317223043
4/0 AWG01*112*4711*141825*36
250 kcmil0011136*9*1115*2029
300 kcmil001*113*571013*1725
350 kcmil001*112*469*111522
400 kcmil0001114*68*101320*
500 kcmil00011135681116
600 kcmil0001*112457*913
700 kcmil0001*112*346*811
750 kcmil0000111345711
800 kcmil00001*11345710
900 kcmil00001*113*3469
1000 kcmil00001*112346*8
1250 kcmil†000001*112*346
1500 kcmil†000001*111235
1750 kcmil†0000001112*34
2000 kcmil†00000011113*4

PVC conduit fill: Schedule 40 vs Schedule 80 quick comparison

Trade size#12 THHN in Schedule 40#12 THHN in Schedule 80
1/2 in86
3/4 in1512
1 in2520

Same-size wires, nipple off, equipment ground counted; Schedule 80 has a smaller interior area at the same trade size.

View the full PVC conduit fill chart: Schedule 40 & 80, THHN & XHHW

Rigid metal conduit (RMC) fill chart: maximum THHN conductors

THHN wire size1/2 in RMC3/4 in RMC1 in RMC1-1/4 in RMC1-1/2 in RMC2 in RMC2-1/2 in RMC3 in RMC3-1/2 in RMC4 in RMC5 in RMC6 in RMC
14 AWG13*223663*851402003094125318331202
12 AWG9162646*62102146225301387608*877*
10 AWG6*1017*29*396492142189244383552
8 AWG3691622375382*109140221*318
6 AWG2*47*121627*385979*101159230
4 AWG124710162336486298141
3 AWG11368142031*4153*83120*
2 AWG113571117*26*344470*100
1 AWG1114*5812192533*5174
1/0 AWG1*11347101621274363*
2/0 AWG01123681318233652
3/0 AWG01113571115*193043
4/0 AWG01*112*4691216*25*36
250 kcmil0011135*71013*2029
300 kcmil001113*468111725
350 kcmil001*11235710*1522
400 kcmil001*112*357*81320*
500 kcmil00011124571116
600 kcmil0001*111346*913
700 kcmil0001*111345811
750 kcmil00001113*4*5*711
800 kcmil00001*11234710
900 kcmil00001*112*3469
1000 kcmil00001*1113*4*6*8
1250 kcmil†000001*111246
1500 kcmil†000001*1112*35
1750 kcmil†000000111134
2000 kcmil†0000001*1113*4

* Note 7 increases this maximum count above the strict area result. A fractional part of 0.8 or greater rounds up to the next whole conductor. For a conservative design, avoid using the starred maximum as a target.

† THHN 1250 to 2000 kcmil: Table 5 prints these sizes in a row group shared with THW and RHH, so the area used here is that shared value. Confirm the size is available in your insulation type.

‡ EMT 5 in and 6 in follow NEC 2023 Chapter 9 Table 4 as printed, where these two sizes have the same interior area as RMC. Annex C Table C.1 (informative) lists higher counts for EMT in these two columns, which implies a larger interior area. Chapter 9 is mandatory and governs, so these two columns are the more conservative of the two. If you size 5 in or 6 in EMT close to the limit, confirm with your inspector.

The counts in the EMT and RMC charts on this page are calculated from Chapter 9 Table 4 conduit areas, Table 5 conductor areas and the Table 1 fill limits. They are not copied from the NEC and are not an official NEC chart. We compared every THHN cell in the two charts on this page with the maximum-conductor-count tables in NEC 2023 Annex C (Tables C.1 and C.9, concentric-stranded conductors) and they match, except the EMT 5 in and 6 in columns explained in the ‡ note. Annex C is informative; Chapter 9 is the rule. Compared 2026-10-17.

How to read the chart and check other combinations

  1. Confirm the raceway type and that the wire is THHN. For EMT or RMC, pick the wire size row and the trade size column in the chart that matches your raceway. For PVC Schedule 40 or Schedule 80, use the quick comparison above and read the full Schedule 40 / Schedule 80 pair on the PVC page.
  2. Pick the wire size row.
  3. Pick the trade size column.
  4. Read the maximum number of conductors. A starred count uses Note 7 rounding.

The chart covers one wire size at a time. For mixed wire sizes, other insulation types or a nipple, use the calculator above instead of adding cells from different rows. Any equipment grounding conductor must be included in the chart's total count, not added beyond it.

The EMT and RMC charts use the same wire data and fill limits. Their conduit interior areas differ at the same trade size, so read counts from the chart that matches your raceway. The charts cover THHN only; for XHHW, mixed sizes or a nipple, use the calculator. For PVC Schedule 40 and Schedule 80, see the quick comparison above and the full chart on the PVC conduit fill chart.

Back to the calculator or see the worked example below.

How to use this conduit fill calculator

NEC limits fill to 53% for one conductor, 31% for two, 40% for three or more, and 60% for a qualifying nipple not exceeding 24 in (600 mm). The tool answers three questions with different input requirements: which conduit is the smallest that passes, what the fill percentage is for a conduit you choose, and how many conductors a conduit can hold.

  1. Add one row for each conductor size or insulation type in the raceway.
  2. Choose the conduit type: EMT (electrical metallic tubing), RMC (rigid metal conduit), PVC Schedule 40 or PVC Schedule 80.
  3. Leave the conduit size on Auto to get the smallest passing trade size, or pick a size to check a specific run. Auto searches the available trade sizes of the selected conduit type using the strict area check, without Note 7 rounding. If none passes, no minimum size is returned.
  4. Turn on the nipple option only for a qualifying nipple installed between boxes, cabinets or similar enclosures and not exceeding 24 in (600 mm). The fill limit becomes 60%.
  5. Read the total conductor area, the allowable fill area, the fill percentage, the pass or fail result and the limit the tool applied.

A Note 7 allowance is shown separately; it does not turn a failed strict fill check into a pass.

For a fill check or minimum-size search, enter the size, insulation and quantity for every conductor group.

For a maximum-count lookup, choose one conductor size and insulation type and a specific conduit type and trade size; this mode does not calculate spare capacity around mixed conductor groups.

How conduit fill works

What conduit fill measures

Conduit fill is the percentage of a raceway's usable interior area taken up by the conductors inside it. The calculation compares cross-sectional areas, so it gives the same answer whether the circuit is single-phase or three-phase.

Fill limits at a glance

ConditionMaximum fill
1 conductor53%
2 conductors31%
3 or more conductors40%
Qualifying nipple, not exceeding 24 in (600 mm)60%

To check a conduit, add up the area of every conductor and divide by the interior area of the conduit. Expressed as a percentage, that is the fill. The allowable fill area is the conduit area times the limit that applies to your conductor count. The applicable limit is selected from the total conductor count across all groups, not separately for each group. The nipple option changes only the allowable limit, not the total conductor area.

Count the equipment grounding conductor (EGC) toward fill under Table 1, Note 3. Add it as its own conductor group with the correct size, insulation and quantity; the calculator does not add it automatically.

Conductor and conduit area data

Conductor areas come from Chapter 9, Table 5 and conduit interior areas from Table 4. The calculator supports THHN and XHHW selections. The THHN table row also covers THWN and THWN-2; the XHHW row also covers XHHW-2.

Worked example: mixed conductor sizes in 1-inch EMT

This example uses four #6 THHN conductors and one #10 THHN conductor. That is five conductors, so the 40% limit applies. There is one area total for all the groups.

StepResult
Total conductor area, 4 x 0.0507 + 1 x 0.02110.2239 sq in
3/4 in EMT interior area0.533 sq in
Allowable area in 3/4 in EMT at 40%0.2132 sq in
Fill in 3/4 in EMT, 0.2239 / 0.53342.01%, over 40%: fails
1 in EMT interior area0.864 sq in
Allowable area in 1 in EMT at 40%Approximately 0.346 sq in
Fill in 1 in EMT, 0.2239 / 0.86425.91%, under 40%: passes
Smallest passing size1 in EMT

Displayed allowable areas may be rounded; pass/fail uses the unrounded total-area calculation.

The 3/4 in conduit fails the 40% limit, and the 1 in conduit passes, so 1 in is the smallest passing size here. Conductor areas are from NEC Table 5, conduit interior areas from Table 4, and the 40% limit from Table 1.

NEC 2023 conduit fill rules

NEC 2023 Chapter 9 splits conduit fill into three jobs. Table 1 sets the maximum fill percentage for the number of conductors in the raceway. Table 4 gives the interior area of the raceway type and trade size you select. Table 5 gives the area of each conductor by size and insulation.

Confirm the edition adopted in your jurisdiction with the authority having jurisdiction (AHJ). Displayed or printed values may be rounded, but the pass or fail decision is not rounded first. The Note 7 exception for same-size conductor counts is explained under the conduit fill chart.

Transformer feeder conduit workflow

For a transformer feeder, use a sizing tool first, verify protection and available fault current, select the secondary conductors, and then check whether the conductors fit the raceway. Conduit fill is the last space check in that workflow, not a substitute for ampacity or protection calculations.

  1. Size the transformer with the transformer sizing calculator.
  2. Check protection and the fault current with the available fault current calculator.
  3. Select the secondary conductors with the secondary conductor sizing calculator.
  4. Enter those conductors here to find the conduit they fit in.
  5. After the raceway, check the box they land in with the box fill calculator (NEC 314.16).
  6. For conductors 4 AWG and larger, size the pull box they land in with the pull box sizing calculator (NEC 314.28).
  7. Check voltage drop for the conductor run: passing the fill check does not mean the voltage drop is acceptable, so check it separately.

Common limits and what this result does not check

A passing fill result only says that the conductor areas fit within the selected raceway limit. It does not verify ampacity, derating, overcurrent protection, voltage drop, pulling conditions, bends, or local inspection requirements.

Three rules can change your answer:

What the result is not. A passing fill result only says that the conductor areas fit within the selected raceway limit. It does not verify ampacity, derating, overcurrent protection, voltage drop, pulling conditions, bends, or local inspection requirements.

Source.NEC 2023 Chapter 9, Tables 1, 4 and 5, checked against primary-source photographs. Table 1 Notes 3, 4 and 7 cover grounding conductors, qualifying nipples and same-size conductor count rounding. Values on this page were not taken from third-party calculators.

What this does not check

Check the edition your jurisdiction has adopted.

Disclaimer. This calculator is a sizing and checking aid and is not engineering advice; confirm every result with a licensed professional and your AHJ. Conduit areas from NEC 2023 Chapter 9, Tables 1, 4 and 5. Not engineering advice and not a substitute for the code text. Verify against the edition adopted in your jurisdiction and with your Authority Having Jurisdiction — protection decisions affect life safety.

Questions people actually ask

What is conduit fill?

It is the share of a conduit's interior area that the conductors take up. It checks space only, so it does not replace ampacity, voltage drop or fault-current checks.

What are the NEC conduit fill percentages?

53% for one conductor, 31% for two, and 40% for three or more. A qualifying nipple not exceeding 24 in (600 mm) can use 60%. This page follows NEC 2023; confirm the adopted edition with your AHJ.

How many #12 wires fit in 1/2-inch EMT?

9 THHN #12 conductors (9 by the strict area check). This assumes all conductors are the same size, nipple off, with no other conductors in the conduit. Include the equipment grounding conductor in the count.

How many #14 wires fit in 1/2-inch EMT?

12 THHN #14 conductors (12 by the strict area check). This assumes all conductors are the same size, nipple off, with no other conductors in the conduit. Include the equipment grounding conductor in the count.

How many #12 wires fit in 3/4-inch EMT?

16 THHN #12 conductors (16 by the strict area check). This assumes all conductors are the same size, nipple off, with no other conductors in the conduit. Include the equipment grounding conductor in the count.

How many #10 wires fit in 3/4-inch EMT?

10 THHN #10 conductors (10 by the strict area check). This assumes all conductors are the same size, nipple off, with no other conductors in the conduit. Include the equipment grounding conductor in the count.

How many #8 wires fit in 3/4-inch EMT?

6 THHN #8 conductors (5 by the strict area check, and 6 with Note 7 rounding). This assumes all conductors are the same size, nipple off, with no other conductors in the conduit. Include the equipment grounding conductor in the count.

How do I use a conduit fill chart?

Confirm the conduit type and wire insulation, find the wire size row, then read across to your trade size. The number is the maximum same-size conductor count, and starred counts use Note 7. See the chart above. For mixed wire sizes, use the calculator.

Where is the conduit fill chart?

The EMT chart and the RMC chart are just below the calculator. The full Schedule 40 and Schedule 80 PVC charts are on the separate PVC conduit fill chart page. All chart counts are derived from the NEC area data and fill limits, and starred cells apply Note 7 rounding.

How many wires can I fit in PVC conduit?

It depends on the schedule, trade size, insulation and wire size. The full Schedule 40 and Schedule 80 tables for THHN and XHHW are on the PVC conduit fill chart. For mixed wire sizes, use the calculator above with PVC Schedule 40 or PVC Schedule 80 selected.

What is a nipple in conduit fill calculations?

For this tool, the nipple option applies to a qualifying nipple installed between boxes, cabinets or similar enclosures and not exceeding 24 in (600 mm), under Table 1, Note 4. The NEC allows 60% fill for it.

Can I enter multiple wire sizes?

Yes. Add one row per size or insulation type. The tool adds all the areas together. The worked example above mixes #6 and #10 conductors.

Does conduit fill depend on single-phase or three-phase power?

No. Fill compares cross-sectional areas, so the number of phases is not an input.

Does this calculator check ampacity or derating?

No. It checks space only. Use the secondary conductor sizing calculator for ampacity and correction factors.

Which conductor area should I use for THHN, THWN-2 or XHHW?

Use the area from the Table 5 row that matches your selection. The same AWG size can have a different area in different insulation types, so do not use a THHN area for XHHW or apply one row's area to another. The THHN row also covers THWN and THWN-2.

Why can two conduit fill calculators show different results?

They may follow different NEC editions, use different table data, or round differently. Check which edition each tool uses and compare it with the edition your jurisdiction has adopted.

Does this page include a box fill chart?

No — see the box fill calculator (NEC 314.16).

Can I use this chart for Cat6, Cat6a or coax cables?

No. This chart is for THHN power conductors; use the manufacturer's outside diameter for communications cable instead.

How many wires fit in a 1 inch conduit?

It depends on wire size and conduit type. In 1 in EMT, the chart gives up to 35 #14 THHN, 26 #12 THHN or 16 #10 THHN when all conductors are the same size (equipment ground counted). Mixed sizes need the calculator above. PVC Schedule 40 and Schedule 80 counts are on the PVC conduit fill chart, and rigid counts are in the RMC chart below.