Transformer · Percent impedance · DOE range
Transformer Impedance Calculator
Enter kVA, phase and construction type to find the DOE normal impedance range for that band. A known nameplate or manufacturer-stated %Z can be checked against the range. The range never stands in for the impedance of a specific unit.
By Allen Tan · Updated · How results are sourced
Find the Normal Impedance Range
1Transformer
Nameplate kVA. The lookup keeps the value as entered: no rounding and no interpolation.
Only a nameplate or manufacturer-stated value. The tool never fills in a typical value.
2Applicability check
The DOE definition used here covers 60 Hz.
Must be 34.5 kV or less.
Must be 600 V or less.
Choose the matching entry when the unit is one of the 13 excluded types.
Result
Enter the rated kVA, then choose a phase and a transformer type to locate the DOE table row.
Quick Answer: What Does Transformer %Z Tell You?
Percent impedance, written %Z, expresses a transformer’s impedance as a percentage on its rated-voltage and rated-power basis. It helps compare a known nameplate or manufacturer value with a DOE normal range. kVA alone identifies a table row; it does not reveal the impedance of one unit.
The range on this page comes from the US DOE definition. For a distribution transformer in India the figure is set by IS 1180, which gives a minimum rather than a range and does not cover the 22 kV or 33 kV classes; the IS 1180 minimum impedance lookup returns the listed value for a rating and phase.
Normal range is not a typical impedance value
The tables report normal ranges, not a typical single-point impedance. Use the applicable table to classify a confirmed value; use the nameplate or manufacturer documentation to identify the value for one unit.
Use a known %Z for a fault-current calculation
A fault-current estimate needs a confirmed %Z from the nameplate or manufacturer. A table range cannot supply that unit-specific input. Use the known value with the linked fault-current calculator; keep the range as a comparison reference.
With a confirmed nameplate or manufacturer-stated %Z, estimate available fault current with a known %Z.
Transformer Impedance Tables by kVA
Both tables come from the same cited eCFR text. Each table keeps its own scope and source.
Table 1. Normal Impedance Ranges for Liquid-Immersed Transformers
| Phase | Rated power (kVA) | Minimum %Z | Maximum %Z |
|---|---|---|---|
| Single-phase | 10 ≤ kVA < 50 | 1.0 | 4.5 |
| Single-phase | 50 ≤ kVA < 250 | 1.5 | 4.5 |
| Single-phase | 250 ≤ kVA < 500 | 1.5 | 6.0 |
| Single-phase | 500 ≤ kVA < 667 | 1.5 | 7.0 |
| Single-phase | 667 ≤ kVA ≤ 833 | 5.0 | 7.5 |
| Three-phase | 15 ≤ kVA < 75 | 1.0 | 4.5 |
| Three-phase | 75 ≤ kVA < 112.5 | 1.0 | 5.0 |
| Three-phase | 112.5 ≤ kVA < 500 | 1.2 | 6.0 |
| Three-phase | 500 ≤ kVA < 750 | 1.5 | 7.0 |
| Three-phase | 750 ≤ kVA ≤ 5000 | 5.0 | 7.5 |
In the cited text the two tables match cell for cell; each table keeps its original liquid-immersed or dry-type scope and its own source, and the match does not imply identical equipment designs.
Table 2. Normal Impedance Ranges for Dry-Type Transformers
| Phase | Rated power (kVA) | Minimum %Z | Maximum %Z |
|---|---|---|---|
| Single-phase | 10 ≤ kVA < 50 | 1.0 | 4.5 |
| Single-phase | 50 ≤ kVA < 250 | 1.5 | 4.5 |
| Single-phase | 250 ≤ kVA < 500 | 1.5 | 6.0 |
| Single-phase | 500 ≤ kVA < 667 | 1.5 | 7.0 |
| Single-phase | 667 ≤ kVA ≤ 833 | 5.0 | 7.5 |
| Three-phase | 15 ≤ kVA < 75 | 1.0 | 4.5 |
| Three-phase | 75 ≤ kVA < 112.5 | 1.0 | 5.0 |
| Three-phase | 112.5 ≤ kVA < 500 | 1.2 | 6.0 |
| Three-phase | 500 ≤ kVA < 750 | 1.5 | 7.0 |
| Three-phase | 750 ≤ kVA ≤ 5000 | 5.0 | 7.5 |
The dry-type distribution transformer definition starts at 15 kVA, so the 10 to under-15 kVA part of the first row is outside the applicability check on this calculator.
How to Use the Lookup and Read the Formulas
Start with the transformer’s rated power, phase, and construction type. Confirm the frequency, line voltages, and exclusion status before treating the result as applicable. The lookup returns the matching table range; it does not derive a unit’s actual %Z from kVA.
Select a range, then compare a known impedance
Select the phase and construction type, enter rated power, and review the applicability result. If a required condition is unknown, stop at the range lookup and verify the equipment record before relying on the result. Enter a confirmed %Z only for comparison; the formulas that follow have been checked by algebraic derivation and internal consistency, subject to the assumptions stated here.
Formula inventory and assumptions
FLA_3ph = kVA × 1000 / (√3 × V_LL)— For balanced three-phase apparent power; use line-to-line voltage.FLA_1ph = kVA × 1000 / V— For single-phase apparent power; use the winding voltage.Z_base,3ph = V_LL² / (1000 × kVA)— Three-phase base impedance at 100% impedance, using matching line-voltage and kVA bases.Z_ohm = (%Z/100) × Z_base = (%Z/100) × V_LL² / (1000 × kVA)— %Z is on the transformer's own kVA base and rated voltage at the principal tap.Isc = FLA / (%Z/100) = FLA × 100 / %Z— Approximate secondary symmetrical fault current assuming an infinite source; source/cable impedance, resistance and impedance angle are neglected, with no asymmetrical peak or motor feedback; not applicable where %Z varies with tap.
Published Transformer Impedance Examples
These entries show how public manufacturer material reports impedance. The Square D and ABB entries are catalog or design values associated with a product series, not measurements from a named field unit. The Eaton Cooper entry is a handbook rating-band range, so it describes a band and not one transformer. Treat each value according to its label and source. ABB’s cited excerpts do not state voltage for these rows, so the table records that missing detail without filling it from another document. Published examples provide context for comparing a confirmed value with Table 1 or Table 2; they do not establish a universal unit value or replace the equipment nameplate.
Manufacturer-stated dry-type values
| Maker / series | kVA | Phase | Voltage | %Z | Value type |
|---|---|---|---|---|---|
| Square D EX75T3H | 75 kVA | Three-phase | 480 V delta to 208Y/120 V | 4.01% | Manufacturer catalog nominal value |
| ABB LVDTT | 45 kVA | Three-phase | Voltage not stated in the cited excerpt | 3.6% | Manufacturer nominal design value |
| ABB LVDTT | 225 kVA | Three-phase | Voltage not stated in the cited excerpt | 5.0% | Manufacturer nominal design values |
| ABB LVDTT | 300 kVA | Three-phase | Voltage not stated in the cited excerpt | 4.5% | Manufacturer nominal design values |
| ABB LVDTT | 75 kVA | Three-phase | Voltage not stated in the cited excerpt | 6.4% | Manufacturer nominal design value |
Square D EX75T3H source: Schneider Electric product data sheet.
ABB LVDTT source: ABB technical note "LVDTT percent impedance" by Frank Basciano, 2023-07-25. The note states these percentages are nominal values established during design validation and are not routine production tests.
Manufacturer-published liquid-immersed range
| Source | Rating band | %Z | Value type |
|---|---|---|---|
| Eaton Cooper three-pad-mounted handbook, Table 3 | 45–75 kVA | 2.70–5.75% | Manufacturer handbook rating-band range — not a single-unit measured value |
Eaton Cooper source: Eaton document CA202003EN "Three-phase pad-mounted compartmental type transformer", Table 3 Impedance Voltage. The figures were checked against a government mirror copy of the same file (Vermont Public Utility Commission); the Eaton site was not read directly.
Applicability and What the Ranges Do Not Prove
A table result has a defined regulatory scope. Meeting a listed range does not certify a transformer, confirm every project requirement, or establish a design recommendation. Check the operating conditions and transformer classification before using the range for comparison.
DOE distribution-transformer scope
Use the DOE scope only when the unit matches the stated 60 Hz, voltage, capacity, phase, construction, and exclusion conditions. The input line voltage must be no more than 34.5 kV and the output line voltage no more than 600 V. The selected type and phase also control the capacity limits. An unknown condition does not support an applicability conclusion.
The 13 excluded transformer types
- Autotransformer
- Drive / isolation transformer
- Grounding transformer
- Machine-tool transformer
- Nonventilated transformer
- Rectifier transformer
- Regulating transformer
- Sealed transformer
- Special-impedance transformer
- Testing transformer
- Transformer with a tap range of 20% or more
- Uninterruptible power supply (UPS) transformer
- Welding transformer
Normal versus special impedance
A normal range is a classification reference, not an efficiency value, design target, acceptance tolerance, or electrical-safety proof. A known value outside the listed range may relate to the special-impedance category, which is excluded from the ordinary distribution-transformer scope. That comparison does not diagnose a defect or settle a project qualification. The tables also do not provide an applicability conclusion for a 50 Hz unit.
Version Notes and Different Reference Frameworks
Current text versus the 2014 tables
The lookup uses the current text, checked 2026-10-31, following the 2025-09-09 editorial note. One documented comparison: the ABB LVDTT 75 kVA three-phase dry-type catalog value of 6.4% falls in the current band of 75 ≤ kVA < 112.5 with a normal range of 1.0–5.0%, which puts it 1.4 percentage points over the upper limit. Under the 2014 dry-type three-phase band of 15–150 kVA with a range of 1.5–6.0%, the same value sits 0.4 percentage points over the upper limit. Both readings place the value outside the normal range; only the margin differs.
Schneider's NEMA-based FAQ is a separate reference
Schneider's FAQ states a NEMA basis, a different frame from the CFR tables, and is linked here without copying its figures: Schneider Electric FAQ FA383793.
Frequently Asked Questions
What is transformer percent impedance?
Percent impedance, or %Z, expresses transformer impedance as a percentage on its rated basis. It supports comparison with Table 1 or Table 2. It is not a unit measurement unless a nameplate or manufacturer source identifies it.
Can kVA alone tell me my transformer's %Z?
No. kVA, phase, and type identify a table range. They do not determine the impedance of one transformer. Use a confirmed nameplate or manufacturer-stated %Z for a unit-specific comparison or fault-current estimate.
What is a typical transformer impedance?
The tables provide normal ranges, not a typical single-point impedance. A range cannot supply a unit value. Check the equipment nameplate or manufacturer documentation, then compare that confirmed %Z with the applicable Table 1 or Table 2 range.
Why are the liquid-immersed and dry-type tables identical?
The cited current text has matching cells in Table 1 and Table 2. The tables still retain separate liquid-immersed and dry-type scope and sources. The matching values do not prove that the equipment designs are identical.
How do I check a 75 kVA three-phase transformer?
Select three-phase and the construction type, then locate the 75 kVA row in the matching table. Enter a confirmed %Z to compare it with that range. Do not use a published sample as a substitute for the unit’s own documentation.
Does an impedance outside the range mean the transformer is defective?
No. The range comparison does not diagnose a defect or provide a full qualification decision. A result outside the range may relate to special impedance, an excluded category, different conditions, or a different reference framework.
Can I use these tables for a 50 Hz transformer?
The applicability definition used for these tables covers 60 Hz units. Do not treat a 50 Hz transformer as covered by this lookup. A separate standard or engineering review is needed for that operating condition.
Do published examples show measured nameplate impedance?
Not necessarily. The examples identify catalog nominal values, manufacturer design values, or a handbook rating-band range. Those labels do not make the entries independent nameplate measurements for a specific transformer.
Why does another document show a different impedance range?
Documents can use a different version, scope, or reference framework. Review the version notes and source label before comparing values. Do not merge a separate framework with the current Table 1 or Table 2 range.
How do I use a known %Z to estimate fault current?
Use a confirmed nameplate or manufacturer-stated %Z as the input for the fault-current calculator. A Table 1 or Table 2 range is not a substitute for that value. Follow the linked calculator’s inputs and calculation limits.
Related Electrical Calculators
The full set of tools lives in the calculator index. When the kVA rating itself is still open, review transformer sizing first. With a confirmed nameplate or manufacturer-stated %Z, estimate available fault current with a known %Z. Once the kVA rating and the impedance range are settled, check primary and secondary protection with the fuse and breaker size calculator. Once load current and conductor conditions are settled, verify secondary conductor ampacity with the secondary conductor sizing calculator. With settled load current, conductor metal, length and raceway, check circuit voltage drop.
Transformer Sizing Calculator
Load in kW, kVA or amps to required kVA, the next standard transformer size, and the full-load current on both sides.
OpenTransformer Fuse & Breaker Size Calculator
Primary and secondary overcurrent protection up to 34.5 kV, with a pass/fail check and the code article behind every number.
OpenAvailable Fault Current Calculator
Fault current from transformer kVA, voltage and nameplate %Z, then through each cable run by the point-to-point method.
OpenSecondary Conductor Sizing Calculator
Ampacity with ambient correction, conductor-count adjustment and terminal limits, showing which constraint decided the size.
OpenSources and Data Version
The current 10 CFR 431.192 text and its Table 1 and Table 2 ranges were checked on 2026-10-31, following the 2025-09-09 editorial note. Manufacturer examples retain their reported value type. The listed formulas were checked by algebraic derivation, dimensional analysis and internal consistency on 2026-10-31; their stated assumptions define the limits of use, and they are not presented as calculation logic.
- DOE distribution transformer definition and Tables 1–2: 10 CFR 431.192; current text checked 2026-10-31; text following the 2025-09-09 editorial note.
- Manufacturer-stated sample documents: publisher links are listed with each example group; value-type labels identify catalog, design, or band-range figures.
- Square D EX75T3H sample: Schneider Electric product data sheet; accessed 2026-10-31.
- ABB LVDTT samples: ABB technical note "LVDTT percent impedance" by Frank Basciano, 2023-07-25; accessed 2026-10-31.
- Eaton Cooper band-range sample: Eaton document CA202003EN, Table 3 Impedance Voltage, figures checked against a government mirror copy; accessed 2026-10-31.
- Schneider Electric FAQ FA383793 (NEMA-based reference, figures not reproduced here).
Disclaimer. Ranges from 10 CFR 431.192 Tables 1–2, current text checked 2026-10-31. A DOE normal-range lookup for comparing a known %Z, not a nameplate value, a design recommendation or an equipment qualification. Not engineering advice and not a substitute for the code text. Verify against the edition adopted in your jurisdiction and with your Authority Having Jurisdiction — protection decisions affect life safety.