Motor FLA · NEC 430.248 / 430.250 · single / three-phase

Motor FLA Chart & Calculator

Look up motor amps (FLA) from NEC Table 430.248 in the single-phase chart or Table 430.250 in the three-phase induction chart.

By · Updated · How results are sourced

1Motor

Phases

Three-phase induction section covers 1/2 through 200 HP. 115 V exists only through 2 HP; 2300 V starts at 60 HP.

208 V and 230 V are separate columns. Use the column that matches the motor nameplate voltage.

Selects the Table 430.52(C)(1) row. Design B energy-efficient changes only the instantaneous-trip breaker limit (1100% instead of 800%); wound-rotor lowers the fuse and inverse-time breaker limits to 150%.

2Nameplate and service factor

Overload basis
Service factor

A marked temperature rise of 40 °C or less also allows the 125% level. If you do not have the nameplate, leave this on the lower level.

NEC 2023 Table 430.250 (induction section)

14.0 A full-load current

10 HP three-phase motor at 460 V

Branch-circuit conductors, min ampacity (125%)
17.50 A
Inverse-time breaker, max (250% computed)
35.00 A → 35 A device
Dual-element fuse, max (175% computed)
24.50 A → 25 A device
Nontime fuse, max (300% computed)
42.00 A → 45 A device
Instantaneous-trip breaker (MCP), max setting (800%)
112.00 A
Separate overload device (115% of nameplate)
16.10 A
Thermal protector ultimate trip (156% of table FLA)
21.84 A
Disconnecting means, min current rating (115%)
16.10 A

This uses the example 10 HP three-phase motor at 460 V. Enter your own values to get your result.

NEC 430.32(A)(1), percent of motor nameplate FLC. NEC 430.32(A)(2), percent of Table 430.248/250 FLA.

No nameplate current entered, so the table FLA stands in for it. Use the nameplate value for the real overload setting.

Where the table value is not enough for the starting current, 430.52(C)(1)(b) allows up to 400% nontime fuse (<= 600 A) / 225% dual-element fuse / 400% inverse-time breaker (FLC <= 100 A) or 500% (FLC > 100 A). Not computed here.

An instantaneous-trip breaker is permitted only as part of a listed combination motor controller with coordinated overload protection (430.52(C)(3)). If the table setting will not let the motor start, 430.52(C)(3) allows up to 1300% (1700% for Design B energy-efficient / premium efficiency). Not computed here.

The 115% figure is the general current-rating rule in 430.110(A). Its exception lets a listed motor-circuit switch (unfused) have a current rating below 115% when its horsepower rating is at least the motor horsepower, so check the switch listing for both ratings.

Share this result

https://kvcalc.com/tools/motor-fla-calculator/

✉ Email
Post to social

The link carries the full calculation, so anyone opening it lands on the same inputs and the same result.

Look up motor full-load current (full load amps) from NEC Table 430.248 (single-phase) or Table 430.250 (three-phase induction), then size the branch-circuit conductors, breaker and fuses, overload device and disconnect. Use the calculator above, or if you only need the table value, go straight to the single-phase or three-phase motor FLA chart (a 3 phase motor amps chart). Table values govern conductor ampacity, switch ratings and branch-circuit protection per 430.6(A)(1); the separate overload device follows the nameplate per 430.32(A)(1).

Motor FLA chart: single-phase, Table 430.248 (amperes)

Single-phase motor FLA chart. NEC 2023 Table 430.248 basis, all four voltage columns. Find the HP row and read across to the voltage column.

HP115 V200 V208 V230 V
1/64.42.52.42.2
1/45.83.33.22.9
1/37.24.143.6
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88
1-1/22011.51110
22413.813.212
33419.618.717
55632.230.828
7-1/280464440
1010057.55550

Motor FLA chart: three-phase induction, Table 430.250 (amperes)

Three-phase motor FLA chart, induction (squirrel-cage / wound-rotor) section of NEC 2023 Table 430.250. The synchronous unity-power-factor section is not included.

HP115 V200 V208 V230 V460 V575 V2300 V
1/24.42.52.42.21.10.9—
3/46.43.73.53.21.61.3—
18.44.84.64.22.11.7—
1-1/2126.96.6632.4—
213.67.87.56.83.42.7—
3—1110.69.64.83.9—
5—17.516.715.27.66.1—
7-1/2—25.324.222119—
10—32.230.8281411—
15—48.346.2422117—
20—62.159.4542722—
25—78.274.8683427—
30—9288804032—
40—1201141045241—
50—1501431306552—
60—177169154776216
75—221211192967720
100—2852732481249926
125—35934331215612531
150—41439636018014437
200—55252848024019249

A dash (—) means the printed table has no value for that HP and voltage combination; the lookup never interpolates or estimates. The 115 V column ends at 2 HP and the 2300 V column starts at 60 HP, exactly as printed. 208 V and 230 V are separate columns: use the one that matches the motor nameplate voltage, never one in place of the other.

Back to the calculator or see the worked example below.

How to use this motor FLA calculator

The tool looks up the table FLA (motor amps) for one motor and sizes its branch circuit below: branch-circuit conductors, breaker and fuses, overload device and disconnect.

  1. Choose single-phase (Table 430.248) or three-phase (Table 430.250, induction section).
  2. Pick the HP row and the voltage column. A combination with no printed value is reported, not estimated.
  3. For three-phase motors, choose the motor type for the Table 430.52(C)(1) protection percentages.
  4. If you have the nameplate current, enter it for the separate overload device; otherwise the table FLA is used as a placeholder and the result says so.
  5. Read the table FLA and its table reference, the minimum conductor ampacity, the maximum protection settings with their standard devices, the instantaneous-trip (MCP) setting, the overload setting, the thermal protector trip and the minimum disconnect rating.

How motor branch-circuit sizing works

Table current vs nameplate current

430.6(A)(1) requires the Table 430.248 / 430.250 values, not the nameplate, for conductor ampacity, switch ratings and branch-circuit short-circuit / ground-fault protection ratings. The separate overload device is the exception: it follows the nameplate current under 430.32(A)(1).

Branch-circuit rules at a glance

ItemRule
Branch-circuit conductorsAt least 125% of table FLA (430.22, single continuous-duty motor)
Inverse-time breaker, maximum250% of FLA, next higher standard rating if off-list (430.52(C)(1)(a))
Dual-element fuse, maximum175% of FLA, next higher standard rating if off-list (430.52(C)(1)(a))
Nontime fuse, maximum300% of FLA, next higher standard rating if off-list (430.52(C)(1)(a))
Instantaneous-trip breaker (MCP), maximum800% of FLA (1100% Design B energy-efficient / premium); trip setting, not rounded; only in a listed combination motor controller (430.52(C)(3))
Separate overload device125% of nameplate (service factor 1.15 or higher) or 115% otherwise (430.32(A)(1))
Disconnecting meansAt least 115% of FLA (430.110(A), 1000 V or less)

Standard fuse and breaker ratings come from 240.6(A). Where the table percentage is not enough for the starting current, 430.52(C)(1)(b) allows higher settings; the calculator reports that allowance as a note and does not compute it.

Worked example: 10 HP three-phase motor at 460 V

This example uses a 10 HP three-phase squirrel-cage motor at 460 V with no nameplate value entered and the service factor not known, so the lower 115% overload level and the table FLA stand in.

StepResult
Table FLA, NEC 2023 Table 430.250 (induction section)14 A
Branch-circuit conductors, 125% of 14 A17.50 A minimum ampacity
Inverse-time breaker, 250% = 35.00 A35 A device
Dual-element fuse, 175% = 24.50 A25 A device
Nontime fuse, 300% = 42.00 A45 A device
Instantaneous-trip setting, 800% = 112.00 Amaximum trip setting
Separate overload, 115% of nameplate basis16.10 A
Thermal protector trip, 156% of table FLA21.84 A
Disconnect, 115% of 14 A16.10 A minimum

Devices take the next higher standard 240.6(A) rating where the computed maximum matches no standard size. Enter your own HP, voltage and motor type in the calculator above for your result.

NEC 2023 motor rules behind this page

Article 430 splits motor branch circuits into separate jobs. Tables 430.248 and 430.250 give the full-load current by HP and voltage. Section 430.22 sizes the branch-circuit conductors, Table 430.52(C)(1) caps the short-circuit / ground-fault protection, 430.32 covers overload and thermal protection, and 430.110(A) sizes the disconnecting means.

Confirm the edition adopted in your jurisdiction with the authority having jurisdiction (AHJ). This page covers single-phase motors and three-phase squirrel-cage induction motors; synchronous, two-phase, DC and multispeed or part-winding variants are outside this calculator.

Motor branch-circuit workflow

For a motor branch circuit, look up the table FLA first, then size each part of the branch in order. The FLA lookup is the first step, not a substitute for protection or disconnect calculations.

  1. Look up the table FLA on the chart or with the calculator.
  2. Size the branch-circuit conductors with the secondary conductor sizing calculator for ampacity and correction factors.
  3. Check protection and the fault current with the available fault current calculator.
  4. Select the disconnect at no less than 115% of the table FLA.

Common limits and what this result does not check

Three rules can change your answer:

What the result is not. A table FLA only identifies the current the Code assigns to that HP and voltage. It does not verify voltage drop, starting performance, duty cycle, multispeed or part-winding connections, multi-motor feeders, or local inspection requirements.

Source.NEC 2023 Article 430, Tables 430.248, 430.250 and 430.52(C)(1), with standard ratings from 240.6(A). FLA values were transcribed cell by cell from NEC page images; percentages are as printed. Values on this page were not taken from third-party calculators.

Check the edition your jurisdiction has adopted.

Disclaimer. This calculator is a sizing and checking aid and is not engineering advice; confirm every result with a licensed professional and your AHJ. FLA values from NEC 2023 Tables 430.248 and 430.250; branch-circuit rules from Article 430. Not engineering advice and not a substitute for the code text. Verify against the edition adopted in your jurisdiction and with your Authority Having Jurisdiction — protection decisions affect life safety.

Questions people actually ask

Should I use the NEC table FLA or the motor nameplate FLA?

Use the table value for conductor ampacity, switch ratings, and branch-circuit short-circuit / ground-fault protection: 430.6(A)(1) requires the Table 430.248 / 430.250 values, not the nameplate, for those items. For example, a 10 HP three-phase motor at 460 V takes 14 A from the table. Use the nameplate only where the Code says so, such as the separate overload device below.

What size conductors does a motor need? (the 125% rule)

For a single continuous-duty motor, branch-circuit conductors must have an ampacity of at least the table FLA times 125% (430.22). A 10 HP three-phase motor at 460 V draws 14 A from the table, so its conductors need at least 17.50 A of ampacity. Then apply temperature correction, bundling adjustment and terminal limits as usual.

What are the 250% / 175% / 300% breaker and fuse settings?

Table 430.52(C)(1) caps branch-circuit short-circuit / ground-fault protection at 250% of FLA for an inverse-time breaker, 175% for a dual-element (time-delay) fuse and 300% for a nontime fuse, with the next higher standard rating where the computed value is off-list. On the 10 HP / 460 V example (14 A): breaker 35.00 A, so a 35 A device; dual-element fuse 24.50 A, so a 25 A device; nontime fuse 42.00 A, so a 45 A device.

Can I use the 230 V column for a 208 V motor?

No. 208 V and 230 V are separate printed columns with different values: a 10 HP three-phase motor reads 30.8 A at 208 V but 28 A at 230 V. Always read the column that matches the motor nameplate voltage.

Why is there no 115 V value for larger three-phase motors?

The printed Table 430.250 stops the 115 V column at 2 HP. A larger combination has no value to read: NEC 2023 Table 430.250 (induction section) lists no value for 5 HP at 115 V. Size from a listed voltage column instead.

Where does the 2300 V column start?

The printed Table 430.250 starts the 2300 V column at 60 HP (16 A there). Below that there is nothing to read: NEC 2023 Table 430.250 (induction section) lists no value for 50 HP at 2300 V.

What is the FLA of a 5 HP single-phase motor at 115 V?

Table 430.248 lists 56 A for 5 HP single-phase at 115 V. Its branch-circuit conductors need at least 70.00 A (125% of 56 A).

How is the motor disconnect sized? (the 115% rule)

The disconnecting means must be rated at least 115% of the table FLA (430.110(A), 1000 V or less). The 10 HP / 460 V example (14 A) needs a disconnect rated at least 16.10 A.

How is the separate overload device set? (125% vs 115%)

Unlike the items above, the separate overload device follows the motor nameplate current: 125% where the service factor is 1.15 or higher (or the marked rise is 40 °C or less), otherwise 115% (430.32(A)(1)). On the 10 HP / 460 V example with no nameplate entered and the service factor not known, the calculator uses 115% of the table FLA as a stand-in, 16.10 A. Enter the nameplate current for the real setting.

What is an instantaneous-trip breaker (MCP) setting for a motor?

An instantaneous-trip breaker (MCP) is a trip setting, not a frame rating: at most 800% of the table FLA (1100% for Design B energy-efficient / premium efficiency motors), with no round-up to a standard size, and only as part of a listed combination motor controller with coordinated overload protection (430.52(C)(3)). Where the table setting will not let the motor start, 430.52(C)(3) allows up to 1300% (1700% for Design B energy-efficient / premium efficiency). On the 10 HP / 460 V example (14 A) the maximum trip setting is 112.00 A.

Does the 115% disconnect rule apply to the horsepower rating?

No. The 115% rule in 430.110(A) is a current rating: the disconnecting means must have a current rating of at least 115% of the table FLA (1000 V or less). Its exception lets a listed motor-circuit switch (unfused) have a current rating below 115% when its horsepower rating is at least the motor horsepower, so check the switch listing for both the current and the horsepower ratings.

Where is the motor FLA chart?

The charts are just below the calculator: the single-phase Table 430.248 chart and the three-phase Table 430.250 induction-section chart. If you came looking for a motor amps chart, these two tables are that reference: find the HP row, read across to the voltage column, and a dash means the printed table has no value there. For conductor, breaker, overload and disconnect sizing from a chart value, use the calculator.