NEC 310.16 · 310.15 · 110.14(C) · 2023 Code

Secondary Conductor Sizing Calculator

Pick the transformer rating and the installation conditions. The tool sizes the conductors and shows which constraint decided it.

1Transformer secondary

kVA
Phase
Load type

NEC 215.2(A)(1): continuous load plus 100% of any non-continuous load. If unsure, keep Continuous.

2Conductor

Material
Insulation rating

A higher rating gives more headroom for derating. THHN in conduit is 90 °C.

Installation conditionsTerminals, ambient temperature, conductor count
Equipment terminal rating

NEC 110.14(C) caps the usable ampacity at this column even with 90 °C wire.

30 °C is the baseline for Table 310.16.

1–3 band. Equipment grounding conductors never count; whether a neutral counts depends on the circuit — see the FAQ below.

Each must be at least 1/0 AWG under NEC 310.10(H).

Conductor per phase

4/0Cu

Single copper conductor per phase

✓PASS

Each 4/0 conductor carries 225.5 A against an allowable 230 A.

How that size was reached

  1. 1
    Load to be carried180.4 A total

    One conductor per phase

  2. 2
    Continuous-load factor× 1.25

    NEC 215.2(A)(1): 180.4 A × 1.25 = 225.5 A design current

  3. 3
    Required per conductor225.5 A

    Each conductor must carry at least this after all correction

  4. 4
    Base ampacity — 4/0 Cu, 90 °C column260 A

    NEC 310.16, at 30 °C ambient with up to 3 current-carrying conductors

  5. 5
    Ambient temperature correction× 1.00

    NEC 310.15(B)(1), 26–30 °C ambient on a 90 °C conductor

  6. 6
    Adjustment for conductor count× 1.00

    3 current-carrying conductors — no adjustment

  7. 7
    Corrected ampacity260 A

    260 A × 1.00 × 1.00

  8. 8
    Terminal limit — 75 °C column230 A

    NEC 110.14(C): the ampacity cannot exceed the terminal temperature column, even with better insulation

  9. 9
    Allowable ampacity230 A

    Governed by the terminal rating

Key figures

Secondary load current
180.4 A
Design current (125%)
225.5 A
Required per conductor
225.5 A
Corrected ampacity
260 A
Terminal limit
230 A
Allowable ampacity
230 A
Limited by
terminal rating

Code references

  • — NEC 215.2(A)(1) — conductors sized for 125% of the continuous load
  • — NEC 310.16 — allowable ampacities, 30 °C ambient, 3 or fewer conductors
  • — NEC 310.15(B)(1) — ambient temperature correction factors
  • — NEC 310.15(C)(1) — adjustment for more than three current-carrying conductors
  • — NEC 110.14(C) — conductor temperature rating limits at equipment terminations

Share this result

https://kvcalc.com/tools/secondary-conductor-sizing-calculator/

✉ Email
Post to social

The link carries the full calculation, so anyone opening it lands on the same inputs and the same result.

Conductor per phase · 150 kVA

4/0Cu

✓ PASS
2026 NEC note. The 2026 edition renumbers some of the provisions used here: continuous-load sizing is in 215.4(A)(1), parallel conductors are in 310.10(G), and Table 310.16 includes 16 AWG copper and a 14 AWG row whose aluminum-column values are footnoted for copper-clad aluminum only. This chart currently runs the 2023 NEC data set and does not mix those new rows into the result. Confirm the edition adopted by your AHJ.

Why the order of operations matters

Sizing is not one multiplication. Correction and adjustment run against theinsulation rating, then the result is capped by theterminal rating. Applying every factor to the terminal column — the most common shortcut — under-derates and pushes you to a larger, more expensive conductor.

Step 1

Start at 90 °C

Look up the size in the column matching the conductor insulation, not the terminals. THHN in conduit gives you the 90 °C numbers.

Step 2

Apply both factors

Multiply by the ambient correction and by the 310.15(C)(1) conductor-count adjustment. Both come off the same starting ampacity.

Step 3

Cap at the terminal

NEC 110.14(C) limits the answer to the terminal column. Whichever of the two is lower is the ampacity you may actually use.

NEC Table 310.16 ampacities at a glance

Base values at 30 °C ambient with not more than three current-carrying conductors. The calculator applies correction and adjustment on top of these.

Copper

Size60 °C75 °C90 °CAdjustment 4–67–910–20
14 AWG152025201813
12 AWG202530242115
10 AWG303540322820
8 AWG405055443928
6 AWG556575605338
4 AWG708595766748
3 AWG85100115928158
2 AWG951151301049165
1 AWG11013014511610273
1/012515017013611985
2/014517519515613798
3/0165200225180158113
4/0195230260208182130
250 kcmil215255290232203145
300 kcmil240285320256224160
350 kcmil260310350280245175
400 kcmil280335380304266190
500 kcmil320380430344301215
600 kcmil350420475380333238
700 kcmil385460520416364260
750 kcmil400475535428375268
800 kcmil410490555444389278
900 kcmil435520585468410293
1000 kcmil455545615492431308
1250 kcmil495590665532465333
1500 kcmil525625705564493353
1750 kcmil545650735588515368
2000 kcmil555665750600525375

The last three columns are the 90 °C value with only the 310.15(C)(1) conductor-count adjustment applied. Ambient temperature correction and the terminal limit must be checked separately; these adjusted columns are not final allowable ampacities.

Aluminium

Size60 °C75 °C90 °CAdjustment 4–67–910–20
12 AWG152025201813
10 AWG253035282518
8 AWG354045363123
6 AWG405055443928
4 AWG556575605338
3 AWG657585685943
2 AWG7590100807050
1 AWG85100115928158
1/01001201351089568
2/011513515012010575
3/013015517514012288
4/0150180205164144103
250 kcmil000
300 kcmil000
350 kcmil000
400 kcmil000
500 kcmil000
600 kcmil000
700 kcmil000
750 kcmil000
800 kcmil000
900 kcmil000
1000 kcmil000
1250 kcmil000
1500 kcmil000
1750 kcmil000
2000 kcmil000

This chart covers aluminum and copper-clad aluminum from 12 AWG upward. It does not include the smaller copper-clad-only entries shown in the supplied 2026 table.

Ambient temperature correction factors

NEC 2023 Table 310.15(B)(1), based on 30 °C. A dash means the code lists no factor for that combination, which usually means the insulation is not adequate there. The 2026 edition separates the 30 °C and 40 °C bases into Tables 310.15(B)(1)(1) and (2); the 40 °C table is not interchangeable with the data shown here.

Ambient °C60 °C conductor75 °C conductor90 °C conductor
10 and below1.291.21.15
11–151.221.151.12
16–201.151.111.08
21–251.081.051.04
26–30111
31–350.910.940.96
36–400.820.880.91
41–450.710.820.87
46–500.580.750.82
51–550.410.670.76
56–60—0.580.71
61–65—0.470.65
66–70—0.330.58
71–75——0.5
76–80——0.41
81–85——0.29

Adjustment for more than three current-carrying conductors

NEC Table 310.15(C)(1). Note the cliff between nine and ten conductors — the factor drops from 70% to 50% in one step.

1–3 conductors

100%no adjustment

4–6 conductors

80%of table ampacity

7–9 conductors

70%of table ampacity

10–20 conductors

50%of table ampacity

21–30 conductors

45%of table ampacity

31–40 conductors

40%of table ampacity

41 and above conductors

35%of table ampacity

Data sources

Questions people actually ask

Why does the tool size for 125% of the transformer current?

Because NEC 215.2(A)(1) sizes feeder conductors for the continuous load at 125% plus 100% of any non-continuous load. A continuous load is one expected to run for three hours or more. The calculator defaults to Continuous because it is the conservative choice. Switch to Non-continuous only if you know the load is intermittent, or if the equipment is listed for operation at 100% of its rating.

Do I use the 90 °C ampacity when the terminals are only rated 75 °C?

Yes — for correction and adjustment you start from the insulation rating, then check the terminal limit separately. NEC 110.14(C) caps the final allowable ampacity at the terminal column, but it does not stop you using the higher insulation column to survive derating. The calculator does both steps in order, which is where most sizing tools get it wrong by applying every factor to the 75 °C column.

Why is the 75 °C or 60 °C column still the limit if I have THHN?

Because the weakest link governs. THHN is rated 90 °C, but the heat has to leave the conductor at the lug. If the busbar is marked 75 °C, the conductor is limited to the 75 °C ampacity of its size, no matter what insulation you pulled in.

Does the neutral count as a current-carrying conductor?

A neutral that carries only the imbalance from the other conductors of the same circuit need not count. Do count the neutral in a 2-wire circuit, in a 3-wire circuit using two phases and the neutral of a 4-wire three-phase wye system, and in a 4-wire three-phase circuit where the major portion of the load is nonlinear. The supplied 2026 text states these cases in 310.15(E)(1) and (2). Enter the count for each raceway or cable, not the total across separate raceways.

What ambient temperature should I use?

30 °C is the Table 310.16 baseline, so no factor applies there. Use the actual air temperature at the hottest part of the run: roughly 40 °C for a shaded outdoor raceway, and 45–50 °C for rooftop or attic work. Above 30 °C the factor eats into your margin quickly — a 90 °C conductor at 50 °C keeps only 82% of its table ampacity.

When do I need parallel conductors?

When no single size in Table 310.16 carries the load after correction. Each parallel conductor must be at least 1/0 AWG under NEC 310.10(H), and every conductor in the paralleled set counts toward the 310.15(C)(1) adjustment.

Does this check the secondary protective device or the 240.21(C) tap rules?

No. It sizes the conductors for ampacity only. Secondary conductor protection under NEC 240.21(C) and the primary protection from the fuse size chart are separate checks, so run both before you finalize a design.

Does this cover voltage drop?

No. Table 310.16 is an ampacity table and the code note says its values are based on temperature alone. Voltage drop is a separate check under Informational Note 210.19(A) and has no code limit — design to it, but do not expect this tool to size for it.

Related calculators

Disclaimer. Based on the 2023 NEC. Not engineering advice and not a substitute for the code text. Verify against the edition adopted in your jurisdiction and with your Authority Having Jurisdiction — protection decisions affect life safety.