Grounding · NEC 250.66 / 250.122 · 2023
NEC Table 250.66 Grounding Electrode Conductor Size Chart + Calculator
Size the GEC from the largest ungrounded service-entrance conductor (Table 250.66). Size the EGC from the rating of the upstream breaker (Table 250.122).
By Allen Tan · Updated · How results are sourced
GEC per Table 250.66
#4Cu/#2Al
- Tab
- A · GEC
- Result
- #4 Cu / #2 Al
Cap note: confirm the Limits section below with your AHJ.
Share this result
https://kvcalc.com/tools/nec-table-250-66/
The link carries the full calculation, so anyone opening it lands on the same inputs and the same result.
How to use Table 250.66
Start with the size of the largest ungrounded service-entrance conductor. For parallel sets, use the equivalent area. Pick the material column: Copper, or Aluminum or Copper-Clad Aluminum (Al/CCA). Read across Table 250.66 to the minimum grounding electrode conductor (GEC) size in the Copper or Aluminum column. If the electrode is only a rod, pipe, or plate, or only concrete-encased, check the caps below before you buy wire. This page follows NEC 2023. Confirm the adopted edition with your AHJ.
How do I size a grounding electrode conductor?
Start from the largest ungrounded service-entrance conductor size and material, then read Table 250.66. Use Tab A of the calculator or the chart below, and check the rod and Ufer caps for those electrode types.
GEC vs EGC: 250.66 vs 250.122
The two conductors answer different questions. Size the GEC from the largest ungrounded service-entrance conductor under Table 250.66. Size the equipment grounding conductor (EGC) from the rating of the upstream overcurrent device under Table 250.122. Tab A asks for a conductor size; Tab B asks for a breaker rating in amperes. Use Tab A for the GEC and Tab B for the EGC, and do not mix the two table values in one result card. Bonding jumper sizing under 250.102 is mentioned here only and gets no separate page.
Table 250.66 chart
Table 250.66 gives the minimum GEC size from the largest ungrounded conductor size. Copper and Al/CCA service conductors use separate input columns, and the GEC output has separate Copper and Al/CCA columns. For parallel sets, the equivalent size follows Table Notes 1–2. Installation restrictions follow 250.64 (Note 3).
| Largest ungrounded Cu | Largest ungrounded Al/CCA | GEC Cu | GEC Al/CCA |
|---|---|---|---|
| 2 or smaller | 1/0 or smaller | 8 | 6 |
| 1 or 1/0 | 2/0 or 3/0 | 6 | 4 |
| 2/0 or 3/0 | 4/0 or 250 | 4 | 2 |
| Over 3/0 through 350 | Over 250 through 500 | 2 | 1/0 |
| Over 350 through 600 | Over 500 through 900 | 1/0 | 3/0 |
| Over 600 through 1100 | Over 900 through 1750 | 2/0 | 4/0 |
| Over 1100 | Over 1750 | 3/0 | 250 |
Version stamp: NEC 2023 Table 250.66 · transcribed 2026-10-22 · verify with your AHJ.
What is the minimum size of a grounding electrode conductor?
The table minimum is the first row: service 2 Cu or smaller, or 1/0 Al or smaller, gives 8 Cu / 6 Al. That row is already no larger than the rod-only cap (not required to be larger than 6 Cu / 4 Al), so the cap does not change this row; the cap only reduces table values larger than the cap. See Limits.
What is the largest size grounding electrode conductor required?
The table maximum is the last row: over 1100 Cu or over 1750 Al gives 3/0 Cu or 250 Al. The table value stops here: larger service conductors do not push it beyond this row.
Table 250.122 chart
Table 250.122 gives the minimum wire-type EGC size from the rating of the overcurrent protective device (OCPD) ahead of the equipment. Wire-type EGCs shall not be smaller than the table value, and need not be larger than the circuit conductors supplying the equipment (250.122(A)). One EGC may serve several circuits in the same raceway, cable, trench, or tray, sized for the largest OCPD (250.122(C)).
| OCPD not exceeding (A) | EGC Cu* | EGC Al/CCA* |
|---|---|---|
| 15 | 14 | 12 |
| 20 | 12 | 10 |
| 60 | 10 | 8 |
| 100 | 8 | 6 |
| 200 | 6 | 4 |
| 300 | 4 | 2 |
| 400 | 3 | 1 |
| 500 | 2 | 1/0 |
| 600 | 1 | 2/0 |
| 800 | 1/0 | 3/0 |
| 1000 | 2/0 | 4/0 |
| 1200 | 3/0 | 250 |
| 1600 | 4/0 | 350 |
| 2000 | 250 | 400 |
| 2500 | 350 | 600 |
| 3000 | 400 | 600 |
| 4000 | 500 | 750 |
| 5000 | 700 | 1250 |
| 6000 | 800 | 1250 |
30 A and 40 A: the table header reads "not exceeding", so use the first row at or above your rating. 30 A and 40 A use the 60 A row (#10 Cu / #8 Al).
* See installation restrictions in 250.120. Where necessary to comply with 250.4(A)(5) or (B)(4), the EGC shall be sized larger than given in this table.
Version stamp: NEC 2023 Table 250.122 · transcribed 2026-10-22 · verify with your AHJ.
Limits: ground rod #6 / Ufer #4
Two caps can reduce the Table 250.66 result. If the GEC connects only to rod, pipe, or plate electrodes (250.52(A)(5) or (A)(7)), it is not required to be larger than 6 AWG copper or 4 AWG aluminum or copper-clad aluminum (250.66(A)). If it connects only to concrete-encased (Ufer) electrodes (250.52(A)(3)), it is not required to be larger than 4 AWG copper (250.66(B)). Both caps apply only when the conductor does not extend on to other electrode types that require larger wire. For a ground ring, the cap follows 250.66(C): not larger than the ring conductor. Ring details are out of scope here. This page covers only the Table 250.66 / 250.122 values and the caps above; electrode construction, installation, bonding jumpers, and rod diameter/count details are out of scope here.
What size wire should I use for grounding rods?
Look up the Table 250.66 value first, then apply the rod, pipe, or plate cap: not required larger than 6 Cu / 4 Al. The cap covers only the portion that is the sole connection to the rod; any run that continues to other electrodes follows Table 250.66.
Do I need 1/2 or 5/8 grounding rod?
Rod diameter is outside this page's table scope; confirm size and listing with your AHJ.
How many grounding rods for a 200 amp service?
Rod count is outside this page's table scope; confirm it with your AHJ.
Worked examples
Example A starts from the service conductor size, not the breaker rating. Example B starts from the breaker rating in amperes, not the service conductor size.
Example A: 200 A residential service, GEC (Tab A)
- Scenario: 200 A residential service; the largest ungrounded service conductors are 2/0 copper, the most common residential service entrance setup (typical residential service).
- Inputs (Tab A): conductor size 2/0, service material Cu, electrode Other or unknown. The result card shows both the Cu and Al GEC; read the Cu value.
- Lookup: the row 2/0 or 3/0 Cu (4/0 or 250 Al) gives GEC Copper 4 AWG.
- Result: #4 copper GEC per NEC 2023 Table 250.66. Verify with your AHJ.
- A 3/0 copper service falls in the same row and also gives #4 copper. For rod-only or Ufer-only electrodes, see Limits.
Example B: EGC by breaker size (Tab B)
- Scenario: branch/feeder circuit with a 100 A upstream breaker; size the wire-type EGC.
- Inputs (Tab B): OCPD rating 100 A. The result card shows both Cu and Al; read the Cu value.
- Lookup: the row 100 gives EGC Copper 8 AWG (Aluminum 6 AWG).
- Result: #8 copper EGC per NEC 2023 Table 250.122. Verify with your AHJ.
- The same table gives 6 Cu / 4 Al at 200 A.
What size grounding electrode conductor for 200A?
With 2/0 copper service conductors, the table gives #4 copper. See Example A for the steps, and confirm the electrode type (Limits) and your AHJ's adopted edition.
What is the NEC code for grounding a 200 amp service?
Start with 250.66 and Table 250.66 for the GEC, and 250.122 and Table 250.122 for the EGC. The exact clause list for a 200 A service depends on the wiring method and electrodes, so verify with your AHJ.
NEC year & AHJ
This page follows NEC 2023. Both charts were transcribed from NEC 2023 on 2026-10-22 (see Sources). Adoption varies by jurisdiction, so confirm the adopted edition and any local amendments with your AHJ. Older table values are not copied, compared, or listed as differences here.
Related tools
- Conduit Fill Calculator: use it after sizing to check that the conductors fit the raceway. You need this when the sized GEC or EGC must pull through the same raceway as the phase conductors.
- Box Fill Calculator: use it when conductors terminate in a box and you need to check box volume. You need this when the grounding conductor lands in the same outlet or junction box and counts toward box fill.
- Voltage Drop Calculator: use it when a long run forces larger circuit conductors, then recheck the EGC size for the larger run.
- Secondary Conductor Sizing Calculator: use it when sizing transformer secondary conductors, then return here for the GEC lookup.
Sources
Forums and Q&A pages are not used as sources. TEP SR-453 is a cross-check for both tables, not the primary source.
| Source | Version / year | Accessed | Used in |
|---|---|---|---|
| S1. NFPA Free Access, NEC Article 250: 250.66 and Table 250.66 with Notes 1–3; 250.66(A)–(C); 250.122(A)–(G) and Table 250.122 with its note | NEC 2023 | 2026-10-22 (transcription date) | Table values, caps, examples (sections 1–6) |
| S2. TEP, MINIMUM SIZE OF BONDING, EQUIPMENT GROUNDING, GROUNDING ELECTRODE CONDUCTORS AND GROUND BUS, No. SR-453, 13 pp. | Revised 2026-07-01 (not verified) | 2026-10-22 | Table 250.66 chart and Table 250.122 chart (cross-check; 30 A / 40 A note) |
| S3. electricallicenserenewal §867: definition sentence for the Table 250.66 lookup (size the GEC from the largest ungrounded conductor) | Year not confirmed | 2026-10-22 | How to use Table 250.66; GEC vs EGC |