Power conversion · kVA · kW · Amps

kVA to Amps / kW to Amps / kVA to kW Calculator

Convert between apparent power, real power and current for DC, single-phase and three-phase systems. Defaults to three-phase 480 V line-to-line.

By · Updated · How results are sourced

1Conversion

kVA

Type a value above zero. The result updates as you type.

2System

System
V

Line-to-line voltage.

Three phase: enter the line-to-line voltage (208, 240, 400, 480, 600). A line-to-neutral value such as 120, 230 or 277 gives amps √3 (1.73×) too high.

kVA to Amps · Three phase

90.21 A

75 kVA (three phase, 480 V)

Formula
A = kVA × 1000 ÷ (√3 × V)
Using
√3 = 1.7320508…

kVA to amps does not use power factor.

This uses the example 75 kVA (three phase, 480 V). Enter your own values to get your result.

Share this result

https://kvcalc.com/tools/kva-kw-amps-calculator/

✉ Email
Post to social

The link carries the full calculation, so anyone opening it lands on the same inputs and the same result.

How it works

Six conversions cover every direction between the three quantities. V is the voltage across the load for DC and single phase, and the line-to-line voltage for three phase. Three-phase current formulas use the exact √3 (√3 = 1.7320508…).

ConversionSingle phase / DCThree phase
kVA to kWkW = kVA × pfkW = kVA × pf
kW to kVAkVA = kW ÷ pfkVA = kW ÷ pf
kVA to ampsA = kVA × 1000 ÷ VA = kVA × 1000 ÷ (√3 × V)
Amps to kVAkVA = V × A ÷ 1000kVA = √3 × V × A ÷ 1000
kW to ampsA = kW × 1000 ÷ (V × pf)A = kW × 1000 ÷ (√3 × V × pf)
Amps to kWkW = V × A × pf ÷ 1000kW = √3 × V × A × pf ÷ 1000

Power factor links kW to the other two quantities but never enters a kVA to amps conversion, because apparent power already contains voltage and current. DC has no reactive power, so power factor is fixed at 1 and DC uses kW only: kW = V × A ÷ 1000. Without a power factor the calculator lists the result for several values of cos φ side by side; that is an even grid, not a recommendation.

Full-load amps table: three phase (amperes)

Rated current for common three-phase transformer sizes at line-to-line voltages, to 0.1 A. Find the kVA row and read across to the voltage column.

kVA208 V (A)240 V (A)480 V (A)600 V (A)
75208.2180.490.272.2
112.5312.3270.6135.3108.3
150416.4360.8180.4144.3
225624.5541.3270.6216.5
300832.7721.7360.8288.7
5001,387.91,202.8601.4481.1

Calculated with the exact value of √3. Some published tables use 1.732 and round differently, so a printed value can differ by 0.1 A.

Source.Table cells are computed on this page from the formulas above with the exact √3; no printed table was copied. Voltages are line-to-line for three phase.

Worked examples

Each example runs through the same conversion the calculator uses, so the numbers always agree with it.

ExampleResult
75 kVA, three phase, 480 V to amps: A = kVA × 1000 ÷ (√3 × V)90.2 A
100 kW, three phase, 480 V, pf 0.8 to amps: A = kW × 1000 ÷ (√3 × V × pf)150.4 A
25 kVA, single phase, 240 V to amps: A = kVA × 1000 ÷ V104.2 A

Back to the calculator for your own values.

Questions people actually ask

How many amps is 1 kVA?

It depends on the voltage and the system. At 240 V single phase, 1 kVA draws 4.17 A (1000 / 240). At 480 V three phase, 1 kVA draws 1.2 A (1000 / (√3 × 480)). Enter your own voltage in the calculator above for your exact current.

What is the difference between kVA and kW?

kVA is apparent power (what the equipment must carry); kW is real power (what the load uses). They are linked by power factor: kW = kVA × pf. A 100 kVA load at 0.8 power factor uses 80 kW, so the remaining capacity is reactive. For motor shaft power, swap kilowatts and horsepower with the kW to HP converter.

Why does kVA to amps not need power factor?

Apparent power already ties voltage to current (kVA = √3 × V × A / 1000 three phase), so no power factor enters. Power factor only converts between kW and kVA or between kW and amps. That is why the calculator hides the power factor field for this direction.

Do I enter line-to-line voltage for three phase?

Yes. Three-phase formulas use the voltage between lines, such as 208, 240, 400, 480 or 600 V. A line-to-neutral value such as 120, 230 or 277 V gives a current √3 (about 1.73×) too high, so check the equipment nameplate first.

How do I convert amps to kW?

Multiply voltage by current, by √3 for three phase, and by power factor: kW = √3 × V × A × pf / 1000. For example, 100 A at 480 V three phase with 0.8 power factor is 66.5 kW. The calculator above runs this in reverse too.

Why is there no kVA option for DC?

DC has no reactive power, so apparent and real power are the same thing and the page uses kW only. Current is simply A = kW × 1000 / V: a 1.2 kW load at 12 V draws 100 A. Power factor is fixed at 1.

Should I size a transformer in kVA or kW?

Size in kVA, because the transformer must carry apparent power including reactive current. Convert the load with kVA = kW / pf first, then pick the next standard size in the transformer sizing calculator.

What is the difference between 240 V single phase and 208 V three phase?

They are different supplies with different formulas: 75 kVA draws 312.5 A single phase at 240 V but 208.2 A three phase at 208 V, so never swap one voltage for the other.

Why does the transformer sizing tool show a slightly different amp value?

That tool rounds √3 to 1.732 while this page uses the exact √3 (1.7320508…), so the two differ only in the fourth significant digit. Both round to 120 A for 100 kVA at 480 V, which is the value you would use.

Related calculators

Disclaimer. This calculator converts between kVA, kW and current with the standard power relations for DC, single-phase and three-phase systems. It is a checking aid, not engineering advice; confirm every result with a licensed professional and your AHJ. Not engineering advice and not a substitute for the code text. Verify against the edition adopted in your jurisdiction and with your Authority Having Jurisdiction — protection decisions affect life safety.