Pull boxes · NEC 314.28 · NEC 2023
Pull Box Sizing Calculator (NEC 2023)
Minimum box length for straight pulls and entry-to-wall distance for single-row angle pulls under NEC 2023 314.28, for pull and junction boxes with insulated 4 AWG and larger. Conductors 18–6 AWG start at the box fill calculator instead.
By Allen Tan · Updated · How results are sourced
Routing first (site routing, not a Code conclusion): 18–6 AWG and any box-volume (cubic-inch) question go to the box fill calculator; only insulated 4 AWG and larger stay on this page (314.28 direction).
This page returns a partial minimum distance for one path with one row per wall only — not a full box size and not a compliance finding. A removable-cover opposite entry, direct cable entry without a raceway, a listed box smaller than (A)(1)/(A)(2), permanent partitions, U pulls, splices, or conduit bodies: tick it in the scope flags and this page refuses it with a prompt to ask your AHJ. Layouts with more than one row per wall, multiple paths, or raceways on a third wall cannot be entered above, so this page does not calculate them — ask your AHJ. Confirm none applies, then read the number.
Scope: what this tool covers — and what it refuses
Covers: insulated conductors 4 AWG and larger, NEC 2023, straight pulls plus single-row angle pulls (one path, one row per participating wall) — minimum controlling dimension only: box length for straight pulls, raceway-entry-to-opposite-wall distance for angle pulls.
Boundary — read before you calculate: conductors 18–6 AWG go to the box fill calculator (Article 314.16 direction); 4 AWG and larger stay on this page (Article 314.28 direction). Volume questions such as cubic inches for an 8×8×4 box are not answered here.
- N1 — entry faces a removable cover: Table 312.6(A) not checked — check the table / ask your AHJ.
- N2 — cable enters directly: no raceway-size transposition in v1 — establish the size via the conduit fill calculator / ask your AHJ.
- N3 — listed box smaller than (A)(1)/(A)(2): not judged — see the product listing file / ask your AHJ (the listed-box clause transcription on file is truncated).
- N4 — permanent partitions: refused in v1 — ask your AHJ.
- Motor terminal housings go to NEC 430.12; power distribution blocks go to 314.28(E) — both refused here.
- U pulls, splices and conduit bodies are refused in v1 — tick them above. More than one row per wall, multiple paths, entries on a third wall, proposed-size back-checks and full depth verification cannot be entered above, so this page does not calculate them — ask your AHJ.
- Millimetre output is not shown: no sourced conversion coefficient is on file, so results are inches only.
Confirm NEC 2023 as your edition; if your jurisdiction adopted another edition, ask your AHJ — unconfirmed version returns no result. A partial minimum is not a full three-dimensional size and not a full NEC compliance finding.
1Code edition & conductors
4 AWG and larger stay on this page; smaller sizes are refused with a pointer to box fill.
2Pull type
Switching pull type keeps your entries and walls but locks the result — re-check the walls, then confirm or edit them before you read a new number. U pulls are not modeled in v1 (see edge cases).
3Raceway entries (nominal trade sizes, inches)
Enter nominal trade sizes in inches (e.g. 2.5, or 4,2,2 for one row of three). Do not enter outside diameters. Any listed standard-size table is intentionally not built in — entries are your declared trade sizes, checked arithmetically only.
Scope flags and edge cases (N1–N4 and v1-out)Tick anything that applies. Each one refuses with a manual-check prompt — this page never judges it compliant.
Minimum controlling dimension — NEC 2023
20.00 in
Box length along the straight-pull axis. Box length along the straight-pull axis.
- Minimum
- 20.00 in
A partial minimum is not a full three-dimensional box size and not a full NEC compliance finding. Inches only — mm conversion is unverified and not shown.
NEC 2023 only; confirm adopted edition with the AHJ.
Local minimum distances only: no full dimensions, depth, listing or compliance verdict.
N1–N4, motor terminals, distribution blocks and complex layouts are not evaluated.
Inches only — metric conversion is not shown.
Share this result
https://kvcalc.com/tools/pull-box-sizing-calculator/
The link carries the full calculation, so anyone opening it lands on the same inputs and the same result.
Before you read the number
This page also covers junction-box sizing at 4 AWG and larger. Run the conduit fill calculator first so the raceway sizes entering the box are already settled, then read the minimum controlling box dimension below under NEC 2023 Article 314.28(A)(1)–(A)(2).
How to Size a Pull Box (NEC 2023)
How to size a pull box or a junction box at 4 AWG and larger — step by step.
Straight pulls
- Identify the largest raceway trade size entering and leaving the box in a straight line.
- The box length in the direction of the raceway axis shall be not less than eight times the trade size of that largest raceway (314.28(A)(1)).
- Diameter here means metric designator (trade size) in nominal inches — do not substitute outside diameters.
This controls the box-length direction (entry-to-exit axis) only; do not mix it with the angle-pull direction.
Angle pulls (single row only in v1)
- For each row on the same wall, take the largest raceway in that row: the distance from each raceway entry to the opposite wall shall be not less than six times its trade size (314.28(A)(2)).
- Increase that distance by the sum of the trade-size diameters of all other raceway entries in the same row on the same wall.
- Calculate each row individually and use the single row that gives the maximum distance.
- If the same conductor enters through two raceways, the distance between those two entries shall be not less than six times the trade size of the larger raceway.
This controls the entry-to-opposite-wall direction only. This page accepts one row per wall on two walls only — anything more complex cannot be entered above and is not calculated here; ask your AHJ. Cable entering directly must first be transposed to the minimum trade-size raceway its conductors require — v1 does not provide that transposition, so direct cable entry without conversion is refused: check the conduit fill calculator or ask your AHJ.
Junction boundary
Junction-box sizing at 4 AWG and larger is covered in this same how-to. Site routing (not a Code conclusion): 4 AWG and larger stay on this page (314.28 direction); 18–6 AWG go to the box fill calculator (box-fill direction). Do not merge the two methods.
NEC Code & Scope (314.28)
The NEC rule for pull boxes is 314.28; the same section covers junction boxes at 4 AWG and larger. Boxes and conduit bodies used as pull or junction boxes shall comply with 314.28(A) through (E). Paragraph (A) applies to raceways with insulated 4 AWG and larger conductors, and cables with 4 AWG and larger conductors.
Not calculated on this page — never judged compliant: N1 removable-cover opposite entry (Table 312.6(A) not checked), N2 direct cable entry (no transposition), N3 listed smaller boxes (clause truncated, not judged), N4 permanent partitions (refused in v1), motor terminal housings (430.12), power distribution blocks (314.28(E)), conduit bodies, U pulls and splices (tick the scope flags to refuse). Proposed-size back-checks and full depth verification cannot be entered above and are not calculated here.
Worked Example
Illustrative example only — not a field answer. Confirm your own layout in the calculator above.
Worked example: What size pull box is needed for 4 inch PVC? Read as a straight pull with 4 in nominal trade size on both walls: 8 × 4 in = 32 in minimum box length (core-computed, NEC 2023 314.28(A)(1)). For comparison, the default straight example (2.5 in trade size both walls) gives 20 in. Angle behaviour is shown in the result table below.
Result Table / Quick Reference
The in-page result table answers the chart intent so no separate chart page is created. All rows below are illustrative examples, not field answers. All values core-computed at build time (NEC 2023, insulated 4 AWG). Standard sizes of pull and junction boxes are intentionally not tabulated: sizes vary by manufacturer and no sourced table is published here.
| Layout | Rule | Minimum controlling dimension |
|---|---|---|
| Straight, 2.5 in both walls (default) | 8 × largest | 20 in box length |
| Straight, 4 in both walls (editor-selected) | 8 × largest | 32 in box length |
| Angle single-row, walls [4, 2, 2] / [2, 2, 2] | 6 × largest + rest, per row | left: 28 in · top: 16 in — governs left at 28 in |
| Same-conductor pair, 4 in ↔ 2 in entries | 6 × larger | 24 in between entries |
Inches only — mm/cm conversion is marked unverified and not shown (no sourced coefficient on file).
Next Tools
- Haven't fixed conduit size or fill yet? Use the conduit fill calculator first — then come back to size the box.
- Working with 18–6 AWG box volume? Use the box fill calculator — 4 AWG and larger stay on this page.
- Box fixed, now sizing the secondary conductors? Use the secondary conductor sizing calculator when you need to size secondary conductors after the box.
- Long pull and worried about drop? Use the voltage drop calculator when you need to check voltage drop after a long pull.
Grounding/ampacity and similar are not linked here — they are covered by other NEC articles, not this page.
What the result is not. A minimum controlling dimension is not a full three-dimensional box size and not a full NEC compliance finding. It does not verify depth, listings, partitions, removable-cover exceptions, U pulls, splices, proposed sizes, or local inspection requirements. This page accepts one row per wall on two walls only; anything more complex is not calculated here — ask your AHJ.
Sources.Rule text: NEC 2023 314.28(A) scope, straight-pull x8, angle-pull per-row x6-plus-rest, same-conductor pair spacing — transcribed from provided excerpts of the 2023 edition on 2026-10-22 (official NFPA link to be added; always check against the copy adopted in your jurisdiction). The 4 AWG split between this page and box fill is a site routing decision, not NEC text. Listed-smaller-boxes clause: the transcription on file is truncated, so this page does not judge it — see the product listing file and ask your AHJ.
Disclaimer. Minimum controlling dimensions from NEC 2023 Article 314.28(A)(1)–(A)(2), transcribed from provided excerpts (official NFPA link to be added). This calculator is a sizing aid and is not engineering advice; confirm every result with a licensed professional and your AHJ. Not engineering advice and not a substitute for the code text. Verify against the edition adopted in your jurisdiction and with your Authority Having Jurisdiction — protection decisions affect life safety.
Questions people actually ask
How do you size a pull box?
Decide straight or angle first. Straight pull: the box length along the raceway axis shall be not less than 8 times the trade size of the largest raceway (NEC 2023 314.28(A)(1)). Single-row angle pull: the distance from each raceway entry to the opposite wall shall be not less than 6 times the largest raceway in that row, plus the sum of the other entries in the same row on the same wall — each row calculated individually, maximum row governs (314.28(A)(2)). Where the same conductor enters through two raceways, those two entries shall be not less than 6 times the larger raceway apart. Multi-row layouts are not calculated on this page — use the calculator above for a supported single-row layout.
What are the standard sizes of pull boxes?
No standard-size table on this page: sizes vary by manufacturer and no sourced table is published here. The result table shows illustrative examples only — not field answers; enter your own layout in the calculator above and confirm a listed box size with the product listing file or your AHJ.
My conductors are smaller than 4 AWG — can I use this page?
No — per site routing (not a verified Code conclusion). Conductors 18–6 AWG go to the box fill calculator (box-fill direction); only 4 AWG and larger stay on this page (Article 314.28 direction).
My box is also a junction / splice box — which rule applies?
Junction-box sizing at 4 AWG and larger follows this same 314.28 how-to. Volume and cubic-inch questions, and box-fill-style junction calculations, live per site routing on the box fill calculator — full detail is there, not duplicated here. Splices and conduit bodies are refused in v1 — tick the scope flags above and ask your AHJ.
Related calculators
Conduit Fill Calculator (NEC Chapter 9)
Fill percentage and smallest raceway for the conductors before they reach the box.
OpenBox Fill Calculator (NEC 314.16)
Pass or fail for 18–6 AWG box volume — 4 AWG and larger stay here.
OpenSecondary Conductor Sizing Calculator (NEC 310.16)
Ampacity with ambient correction and terminal limits.
OpenVoltage Drop Calculator
Volts lost on the run — a box that meets minimum can still drop too much.
Open